| 2006-02-01 00:00:00 | *** DENIED *** |
| | 1) A/C SYSTEM #1 IS TO LARGE FOR 1ST. |
| | FLOOR. MANUAL J IS CALLING FOR 13,965 |
| | SENSIBLE BTU'S + 20% = 16,758 SENSIBLE |
| | BTU'S, SYSTEM BEING INSTALLED IS 17,300 |
| | SENSIBLE BTU'S, UNIT IS 542 SENSIBLE |
| | BTU'S OVER ALLOWABLE SIZE. PER 2001 FBC |
| | CH.13 607.1.ABC.1.1 . |
| | |
| | 2) AIR HANDLER #2 IS A 3 TON ESTIMATED |
| | 1,200 CFM'S, MANUAL J IS CALLING FOR |
| | ONLY 900 CFM'S. THE AHU IS TO LARGE OR |
| | THE DUCTS ARE TO SMALL PLEASE CORRECT. |
| | |
| | 3) AS NOTED IN LAST REVIEW THE RETURN |
| | AIR TRANSFER DUCT TO THE MASTER SUITE IS |
| | TO SMALL, SEE NOTE #4 (C)EXCEPT. |
| | |
| | 4)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 5) 18X18 RETURN AIR GRILL ON 1ST. |
| | FLOOR IS TO SMALL FOR A 3 TON AHU PLEASE |
| | CORRECT. |
| | |
| | 6) ENGINEER'S SEAL MUST APPEAR ON |
| | MECHANICAL PLANS OR HE MUST REMOVE HIS |
| | TITLE BLOCK. |
| | |
| | 7) MECHANICAL CONTRACTOR'S NAME AND |
| | SIGNATURE MUST BE ON MECHANICAL PLANS IF |
| | ENGINEER'S SEALIS NOT. |
| | |
| | 8) NEED TO SHOW BOTH CONDENSER UNITS ON |
| | MECH. PLANS. |
| | |
| | 9) NEED TO SHOW LOCATION OF CONDENSATE |
| | DRAIN LINES AND DRYER VENT ON MECH. |
| | PLANS. |
| | |