| Notes |
| Date |
Text |
| 2005-12-12 00:00:00 | *** DENIED *** | | | 1) NEED TO FILE NOTICE OF COMMENCEMENT. | | | 2) NEED TO SHOW LOCATION OF CONDENSER | | | UNITS ON PLANS. | | | 3) MASTER SUITE 10" RETURN AIR TRANSFER | | | DUCT IS TO SMALL, NEEDS TO BE 12". | | | 1 1/2 TIMES THE SUPPLY AIR TO ALL THE | | | MASTER SUITE. PLEASE REFER TO 2001 FBC/M | | | 601.4 . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|