2005-12-12 00:00:00*** DENIED ***
 1) NEED TO FILE NOTICE OF COMMENCEMENT.
 2) NEED TO SHOW LOCATION OF CONDENSER
 UNITS ON PLANS.
 3) MASTER SUITE 10" RETURN AIR TRANSFER
 DUCT IS TO SMALL, NEEDS TO BE 12".
 1 1/2 TIMES THE SUPPLY AIR TO ALL THE
 MASTER SUITE. PLEASE REFER TO 2001 FBC/M
 601.4 .