2005-11-21 00:00:00*** UNSAT ***
  
 ** PLEASE SEE THAT THE ITEMS BELOW WERE
 REDLINED ITEMS, HOWEVERPLANS ARE
 COMING BACK FOR ZONING COMMENTS, PLEASE
 MAKE THECORRECTIONS AT THIS TIME.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE LIST THE REQUIRED
 DEDICATED BATH CIRCUITS AS 20A AND #12
 210.11C3
  
 2)NOTE: PLEASE SEE GARAGE DOOR OPENER IS
 STILL SHOWN ON PLANS, HOWEVER THE
 DEDICATED CIRCUIT REQUIRED IS NOT ON
 PANEL SCHEDULE OR LOAD CALCS.
 215.5,430.148
  
 3)NOTE: PLEASE SEE REDLINED MISSING
 RECEPTS PER 210.52, TWO MISSING.
  
  
 ** PLEASE SUBMIT THE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  