| 2005-09-14 00:00:00 | ******** UNSAT ********* |
| | |
| | |
| | 1)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:NFPA-72 11.5.1 |
| | |
| | 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 4)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | PLEASE ALSO SEE MISSING GFI RECEPT(S) |
| | FOR MASTER BATH. |
| | |
| | 5)NOTE: PLEASE SHOW GROUNDING ELETRODE |
| | SYSTEM PER 250.50. FOOTER STEEL/COLD |
| | WATER/ ETC. SIZE ALL PER 250.66 |
| | |
| | 6) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E (REAR) |
| | |
| | 7)NOTE: PLEASE SEE MANY AREAS ON PLANS |
| | WHERE RECEPTS ARE REQUIRED TO BE SHOWN |
| | AS GFI/GFI PROTECTED. |
| | 210.8A, 1-7. |
| | BATHS, GARAGES, OUTSIDE , KITCHENS ETC. |
| | |
| | 8)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52, REDLINED ON PLANS. |
| | |
| | 9)NOTE: PLEASE SEE MISSING GDO ON PANEL |
| | SCHEDULE, HOWEVER THIS SI SHOWN ON |
| | PLANS. DEDICATED CIRCUIT. |
| | |
| | 10)NOTE: PLEASE SHOW ALL A/C EQUIPMENT |
| | ON PLANS ALONG WITHALL REQUIRED |
| | DISCONNECTS. |
| | 440.11 |
| | |
| | 11)NOTE: PLEASE ALSO SEE MISSING |
| | RECEPTS/ GFI AND POSSSIBLE LT FOR AHU |
| | AND CU'S. 210.63,210.70 |
| | |
| | 12)NOTE:PLEASE INDICATE THE SERVICE |
| | ENTRANCE CONDUCOTRS FOR RISER AND SIZE |
| | AND TYOE OF CONDUIT BEING USED FOR |
| | RISER. |
| | 215.5, 240.4,310.15B6 |
| | |
| | 13)NOTE: PLEASE VERIFY PANEL SCHEDULE |
| | SHOWS ONE ARC FAULT PROECTED CIRCUIT |
| | FEEDING ALL THREE BEDRMS , RECEPTS, LTS, |
| | ETC.? |
| | |
| | 14)NOTE: PLEASE SEE BEDRMS ETC SHOW AN |
| | ENTIRE RECEPT BEING SWITCHED? PLEASE SEE |
| | RECEPT SPACING AS REQUIRED UNDER 210.52 |
| | ONLY PERMITS HALF OF RECEPT TO BE |
| | SWITCHED, UNLESS AN ADDITIONAL RECEPT IS |
| | ADDED FOR GEN PURPOSE. 210.52 |
| | |
| | 15)NOTE: PLEASE SEE WHAT APPEARS TO BE A |
| | MISSING GFI ALSO FOR KITCHEN PENINSULAR? |
| | 210.52C3 |
| | PLEASE KNOW, RECEPT MORE THAN 6" OUT AND |
| | DOWN CAN NOT BE CONSIDERED THE REQUIRED |
| | GFI RECEPT. |
| | |
| | 16)NOTE: PLEASE SEE EF IN BATHS DO NOT |
| | INDICATE ANY MEANS OF CONTROL, OR SWITCH |
| | LEG ATTACHED. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING ME. |
| | |