2005-09-14 00:00:00******** UNSAT *********
  
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:NFPA-72 11.5.1
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 4)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE ALSO SEE MISSING GFI RECEPT(S)
 FOR MASTER BATH.
  
 5)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E (REAR)
  
 7)NOTE: PLEASE SEE MANY AREAS ON PLANS
 WHERE RECEPTS ARE REQUIRED TO BE SHOWN
 AS GFI/GFI PROTECTED.
 210.8A, 1-7.
 BATHS, GARAGES, OUTSIDE , KITCHENS ETC.
  
 8)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52, REDLINED ON PLANS.
  
 9)NOTE: PLEASE SEE MISSING GDO ON PANEL
 SCHEDULE, HOWEVER THIS SI SHOWN ON
 PLANS. DEDICATED CIRCUIT.
  
 10)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 ON PLANS ALONG WITHALL REQUIRED
 DISCONNECTS.
 440.11
  
 11)NOTE: PLEASE ALSO SEE MISSING
 RECEPTS/ GFI AND POSSSIBLE LT FOR AHU
 AND CU'S. 210.63,210.70
  
 12)NOTE:PLEASE INDICATE THE SERVICE
 ENTRANCE CONDUCOTRS FOR RISER AND SIZE
 AND TYOE OF CONDUIT BEING USED FOR
 RISER.
 215.5, 240.4,310.15B6
  
 13)NOTE: PLEASE VERIFY PANEL SCHEDULE
 SHOWS ONE ARC FAULT PROECTED CIRCUIT
 FEEDING ALL THREE BEDRMS , RECEPTS, LTS,
 ETC.?
  
 14)NOTE: PLEASE SEE BEDRMS ETC SHOW AN
 ENTIRE RECEPT BEING SWITCHED? PLEASE SEE
 RECEPT SPACING AS REQUIRED UNDER 210.52
 ONLY PERMITS HALF OF RECEPT TO BE
 SWITCHED, UNLESS AN ADDITIONAL RECEPT IS
 ADDED FOR GEN PURPOSE. 210.52
  
 15)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 MISSING GFI ALSO FOR KITCHEN PENINSULAR?
 210.52C3
 PLEASE KNOW, RECEPT MORE THAN 6" OUT AND
 DOWN CAN NOT BE CONSIDERED THE REQUIRED
 GFI RECEPT.
  
 16)NOTE: PLEASE SEE EF IN BATHS DO NOT
 INDICATE ANY MEANS OF CONTROL, OR SWITCH
 LEG ATTACHED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  