| Date |
Text |
| 2006-03-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | FROM PREVIOUS REVIEW: |
| | 1. SHT 1 MINIMUM PLUMBING FACILITIES |
| | SHALL BE PER TABLES 1003.1 AND TABLE |
| | 403.1. THIS IS ADDRESSED BY SQUARE |
| | FOOTAGE OF SPACE. PLEASE INDICATE THE |
| | SQUARE FOOTAGE OF THE SPACE BEING |
| | ALTERED.- OCCUPANCY IS SHOWN AS GROUP |
| | A ASSEMBLY. |
| | 2. SHT 1 TOILET ROOMS SHALL COMPLY WITH |
| | SECTION 11-4.22 AND ALL SUBSECTIONS. |
| | DOORS SHALL COMPLY WITH 11-4.13, |
| | CLEAR FLOOR SPACE FOR ALL ACCESSIBLE |
| | FIXTURES REQUIRED. 11-4.22.3 - (SHOW ON |
| | FLOOR PLAN) |
| | TURNING AREA REQUIRED IN EACH TOILET |
| | ROOM. 11-4.22.3 - (SHOW ON FLOOR PLAN) |
| | IF TOILET STALLS ARE PROVIDED, AT LEAST |
| | ONE STALL SHALL COMPLY WITH FIGURE 30E. |
| | A LAV IS REQUIRED IN THE STALL |
| | IF URINALS ARE PROVIDED, THEN ONE SHALL |
| | BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMLIANCE WITH SECTION 11-4.18 AND ALL |
| | SUBSECTIONS. |
| | LAVS SHALL COMPLY WITH 11-4.19 AND ALL |
| | SUBSECTIONS. |
| | |
| | ****************NEW COMMENTS************ |
| | |
| | 1B. A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. PLEASE INDICATE LOCATION |
| | AND SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH 11-4.15 AND ALL SUBSECTIONS. IF NOT |
| | A HI/LOW, ALSO SHOW COMPLIANCE WITH |
| | SECTION 11-4..1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 2B. AS OF JANUARY 01, 2006 ENGINEERS |
| | SHALL US THE NEW TYPE SEAL REQUIRED BY |
| | FLORIDA DEPT OF PROFESSIONAL ENGINEERS. |
| | (SEE ATTACHED SHEET). ALL SHEETS SEALED |
| | AFTER ABOVE DATE WILL BE REQUIRED TO BE |
| | SEALED WITH NEW TYPE SEAL. |
| | 3B.A SERVICE SINK IS REQUIRED PER TABLE |
| | 403.1. SHOW THE LOCATION ON THE FLOOR |
| | PLAN. |
| | 4B. SHOW THE LOCATION OF THE WATER |
| | HEATER. SECTION 104.2.1. |
| | 5B. SHT 2 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. NO WATER IS |
| | SHOWN FOR THE UNINALS. SECTION 104.2.1. |
| | 6B. SHT 2 SANT. RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. ONLY ONE URINAL |
| | IS SHOWN ON THE RISER DIAGRAM.- INDICATE |
| | WHAT THE SANT. LINE BETWEEN THE WATER |
| | CLOSETS CONNECTS TO IN MENS TOILET ROOM |
| | AND WHAT THE SANT. LINE UPSTREAM OF THE |
| | WATER CLOSETS IN THE WOMENS TOILET ROOM |
| | CONNECTS TO. SECTION 104.2.1. |
| | 7B. WATER HEATER REQUIRES THERMAL |
| | EXPANSION CONTROL. SECTION 607.3.2. |
| | 8B. SEE ATTACHED SHEET CONCERNING FS |
| | 553.80(2)(B) AND THE DESIGN |
| | PROFESSIONAL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |