| 2006-02-22 00:00:00 | ********* UNSAT 2ND REVIEW ******** |
| | |
| | *** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH STILL NEED TO BE |
| | ADDRESSED AND SOME NEW COMMENTS DUE TO |
| | INFORMATION ON PLANS. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE SEE RISER |
| | STILL SHOWS THE SAME. |
| | PLEASE KNOW, AN INSPECTION BY THE CHEIF |
| | ELECTRICAL INSPECTOR WAS DONE AND NO |
| | ADDTIONAL ELECTRICAL METER/MAINS WILL BE |
| | PERMITTED WITHOUT A SERVICE CHNAGE TO |
| | INCREASE SERVICE. " ONE SERVICE AND A |
| | MAX OF 6 MAINS, OR ONE MAIN AND THEN |
| | TENANT METERS AND MAINS IN EXCESS OF 6 |
| | WOULD BE PERMITTED AS LONG AS MAIN |
| | SERVICE INSTALLED IS ADEQUATE. |
| | 230.70,230.2, ETC |
| | |
| | ** PLEASE SEE SERVICE RISERS SHOWN |
| | INDICATE MORE THAN 6 MAINS FOR BLDG. |
| | PLEASE SEE THE TWO NEW METERS AND MAINS, |
| | SHOWN ARE NOT PERMITTED.230.2 |
| | |
| | 2)NOTE: OK. NO CHNAGE NEED , ONLY NOTED |
| | FOR INFORMATION. |
| | |
| | **PLEASE SEE REVIEW COMMENTS FROM |
| | OTHER TRADES WHICH WILL AFFECT |
| | ELECTRICAL PLANS. |
| | PLEASE SEE POSSIBLE CHANGE IN |
| | USE/OCCUPANCY INSTENED. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE NEW |
| | COMMENT WITH RESPECT TO ALL CIRCUITING, |
| | PLEASE ALSO SEE THIS COMMENT BELOW. |
| | PLEASE SEE THESE WERE NOT ADDED AS |
| | REQUIRED. |
| | PLEASE INCLUDE EM LTS, NONE COULD BE |
| | LCOATED ON PLANS?? NEW WALLS ETC ARE |
| | BEING SHOW, HALLWAY, HALL ETC, HOWEVER |
| | NO LTS FOR MIN FT CANDLE ARE SHOWN. |
| | PLEASE SEE 7.8.1.3 WHICH REQUIRES A MIN |
| | OF 10 FT CANDLES UNDER NORMAL CONDITIONS |
| | ON ALL STAIR AREAS AND 1FT CANDLE UNDER |
| | EM CONDITIONS. |
| | |
| | ** PLEASE SHOW ALL NEW AND EXISTING |
| | EMERGENCY LT/ EXT LTS AND CIRCUITING PER |
| | 700.12E. THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE SEE NFPA-101 7.8 AND 7.9 |
| | WHICH WILL REQUIRE EM LT FOR EXIT |
| | DISCHARGE FROM 2ND FLR TO PUBLIC RIGHT |
| | OF WAY. |
| | |
| | 4)NOTE: NOTE #4 OK/ NO, PLEASE SEE ONLY |
| | HALF OF THIS NOTE WAS DONE. |
| | PLEASE SEE BATH RMS WILL REQUIRE AN EM |
| | LT BATTERY BACK UP FIXTURE. |
| | LS 101 7.8,7.9 |
| | |
| | ** PLEASE SEE A SWITCHED RECEPT IN |
| | A COMMERICAL OCCUPANCY ISNOT PERMITTED |
| | AS MEANS OF PROVIDING ILLUMINATION. |
| | PLEASE PROVIDE A LIGHTING LAYOUT OF |
| | EITHER EXISTING OR NEW FOR ALL AREAS. |
| | PLEASE ALSO SEE NEW BATH ROOMS WILL |
| | REQUIRE EM LTS. |
| | |
| | 5)NOTE: NOTE #5 OK, LOAD CALCUALTIONS |
| | ADDED, HOWEVER PLEASE SEE ALL CONTINUOUS |
| | LOADS ARE REQUIRED TO BE SHOWN AT 125%. |
| | PLEASE ALSO SEE A/C LOADS WHICH DO NOT |
| | CORRELATE WITH LOAD CALCS. |
| | PLEASE KNOW, SERVICE AS SHOWN LOOKS TO |
| | BE VERY CLOSE IF NOT OVER THE RATING OF |
| | THE SEC'S OF 350 MCM IN RISER. |
| | PLEASE ALSO SEE OPTIONS GIVEN UNDER |
| | 220.35. |
| | |
| | ** PLEASE PROVIDE LOAD CALCUALTIONS |
| | FOR NEW LOADS ADDED TO EXSITING PANEL |
| | AND SERVICE. |
| | 215.5,220.3,220.10,.220.11,220.13 ETC |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| | SHOWN AT 125%. 215.3,230.42 |
| | |
| | 6)NOTE: PLEASE PROVIDE SIGNCIRCUIT PER |
| | 600.5 |
| | |
| | 7)NOTE: NOTE #7 OK?NO, NEW OR EXISTING |
| | RT GFI? |
| | PLEASE SEE COMMENT FOR LOADS FOR A/C |
| | UNITS ABOVE. |
| | |
| | |
| | **PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU/RTU'S.125% MIN. |
| | PLEASE ALSO INDICATE IF NEW OR EXISTING |
| | GFI'S ARE AT ROOF TOP LOCATION FOR |
| | EQUIPMENT. |
| | 210.63 |
| | |
| | |
| | ** NEW NOTES: |
| | |
| | 8)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 9)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FLORIDA STATUES, 553.80(2)(B) WITH |
| | RESPECT TO THE DESIGN PROFESSIONAL AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE AND |
| | PLAN REVIEWS. |
| | PLEASE KNOW, THIS IS ONLY A NOTICE GIVEN |
| | AT THIS TIME. |
| | |
| | |
| | PLEASE BE SURE TO SEE ALL COMMENTS FROM |
| | OTHER TRADES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW.ONCE AGAIN, IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE TO GO OVER |
| | COMMENS OR QUESTIONS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |