Plan Review Notes
Plan Review Notes For Permit 05090176
Permit Number 05090176
Review Stop B
Sequence Number 2
Notes
Date Text
2006-03-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THIS RENOVATION INVOLVES A CHANGE
 OF OCCUPANCY, SEE FBC106.1.1,
 FBC106.4.1.
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 THE BUILDING; TOTAL AREA, BUILDING TYPE
 FBC CHAPTER 6, PROTECTED OR UNPROTECTED,
 SPRINKLED OR UNSPRINKLED.
  
 PROVIDE A LETTER FROM THE ENGINEER, ON
 ENGINEER'S LETTERHEAD, AS TO
 HOW YOU HAVE ARRIVED AT THE TOTAL SF
 AREA.SEE FBC CHAPTER 2, DEFINITIONS.
 PROVIDE AREA CALCULATIONS BROKEN DOWN BY
 FLOOR.SHOW TOTAL SF OF A/C AREA AND
 AREA UNDER THE BALCONY.THE LETTER IS
 TO DECLARE BUILDING SIZE, HEIGHT, TYPE
 FBC600, AND SHOW COMPLIANCE WITH FBC
 TABLE 500.PROVIDE A COPY OF THE
 SURVEY.
  
 4. - 5.)ADDRESSED.
  
 6.)PROVIDE A SITE PLAN SHOWING THE
 BUILDING'S LOCATION ON THE LOT AND THE
 ACCESSIBLE ROUTE, FBC11-4.1.2.
  
 NOT ADDRESSED PROPERLY.A SITE PLAN WAS
 PROVIDED BUT DOES NOT SHOW ACCESSIBLE
 ROUTE.SHOW REQUIRED INFORMATION,
 INCLUDING ACCESSIBLE PARKING.THE
 ACCESSIBLE PARKING SPACE DOES NOT COMPLY
 WITH FBC11-4.6.2 THROUGH 11-4.6.5.ALSO
 SEE ATTACHED FOR DETAIL FOR CITY OF WPB
 STANDARD FOR PARKING.
  
 7.)DECLARE AN OCCUPANT LOAD FOR THIS
 AREA, FBC1003.1, FBC TABLE 1003.1.
  
 NOT ADDRESSED.15 PER SF IS NOT AN
 OCCUPANT LOAD.DECLARE OCCUPANT LOAD;
 SHOULD BE A TOTAL NUMBER.
  
 8.)SHOW REQUIRED OCCUPANCY AND/OR
 TENANT SEPARATIONS.PROVIDE A LISTED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC709.
  
 NO RATED ASSEMBLIES SHOWN.FIRE
 RESISTANCE BETWEEN FIRST AND SECOND
 FLOORS NOT SHOWN.
  
 9.)PROVIDE A CERTIFICATION FOR THE
 FLOOR LOADING FOR THIS OCCUPANCY, FBC
 TABLE1604.1.INCLUDE THE BALCONY.
 PROVIDE DETAILS.
  
 NOT ADDRESSED PROPERLY. A STATEMENT WAS
 ON THE PLAN BUT NO INFORMATION PROVIDED
 FOR THE BALCONY.
  
 10.)PROVIDE ELEVATIONS SO THAT CODE
 COMPLIANCE IN REGARDS TO THE LARGE
 WINDOWS AND THE EXIT STAIR CAN BE
 DETERMINED.
  
 EXTERIOR STAIRS ARE TO COMPLY WITH
 FBC1006.2.2.THE STAIRS SHOWN ARE NOT
 ROOFED OVER.
  
 OPENINGS ARE TO COMPLY WITH FBC1006.2.4.
 SHOW REQUIREMENTS AND COMPLIANCE ON THE
 PLAN.
  
 11.)SEE FBC2405.IS SAFETY GLASS
 REQUIRED?
  
 NOT ADDRESSED.TEMEPERED GLASS IS SHOWN
 FOR THE FIRST FLOOR, WHAT ABOUT THE
 RENOVATION AREA WHICH IS ON THE SECOND
 FLOOR?
  
 12.)PROVIDE A LIFE SAFETY PLAN.SHOW
 ALL EXIT LIGHTS.NOT ENOUGH INFORMATION
 WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.PLEASE REACH FBC CHAPTER 10
 AND SHOW COMPLIANCE ON THE PLAN.SEE
 ALSO FBC11-4.1.3(9).
  
 NOT ADDRESSED, NO LIFE SAFETY PLAN
 PROVIDED.EXITING IS NOT CLEAR.THE
 PLAY AREA SHOWS AN EXIT AT THE DOUBLE
 DOOR, BUT THE TRAVEL DISTANCE TO THE
 STAIR EXCEEDS 150FT AND THAT STAIR
 CANNOT BE USED AS A MEANS OF EGRESS IF
 IT IS NOT COMPLIANT AS AN EXTERIOR
 STAIR.IT SHOULD HAVE TWO EXITS, ONLY
 ONE NON COMPLIANT EXIT SHOWN.PROVIDE A
 LIFE SAFETY AS REQUESTED.
  
 13.)PROVIDE DETAILS AND DESIGN
 CRITERIA FOR BOTH STAIRS AND THE HAND
 RAILS AND STAIR GUARDRAILS, FBC1007 ,
 FBC11-4.9,FBC1015, FBC1608,
 FBC11-4.26.
  
 THE STAIR RAIL WHICH SERVES AS A
 GUARDRAIL DOES NOT COMPLY WITH FBC1015.2
 (HEIGHT).THE EXTENSIONS REQUIRED AT
 THE BOTTOM ARE NOT SHOWN.HANDRAILS
 REQUIRED ON BOTH SIDES, PROVIDE A
 DETAIL.PICKET SPACING NOT SHOWN.
 STRENGTH FOR HANDRAILS WAS PROVIDED BUT
 NOT FOR GUARDRAILS.
  
 14.)PROVIDE A DETAIL AND DESIGN
 CRITERIA FOR THE BALCONY GUARDRAIL.
 FBC1007, FBC1608.
  
 NOT ADDRESSED.
  
 15.)FIRE RATING IS NOT SHOWN BETWEEN
 THE HALL AND THE RECEPTION AREA.THIS
 APPEARS TO BE COMMON AREA, SEPARATION
 REQUIRED.
  
 16.)IF THE WALL BETWEEN THE RECEPTION
 AND HALL IS TO BE RATED, A FIRE RATED
 DOOR REQUIRED FBC TABLE 705.1.2.
  
 NOT ADDRESSED, ONLY SHOWN AS "EXISTING".
  
 17.)IF THIS BUILDING IS NOT FULLY
 SPRINKLED, AREA OF RESCUE ASSISTANCE
 REQUIRED, FBC11-4.1.3(9).IF THIS
 BUILDING IS FULLY SPRINKLED, INDICATE
 AND PROVIDE A SPRINKLER PLAN.
  
 THE AREA OF RESCUE ASSISTANCE IS TO
 COMPLY WITH FBC11-4.3.11.IT IS NOT
 CLEAR HOW AN AREA WITH THREE WALLS, OPEN
 TO THE SPACE, IS AN AREA OF RESCUE
 ASSISTANCE.TWO REQUIRED.
  
 18.)THE SEATING AREA BLOCKS THE
 REQUIRED EGRESS WIDTH OF THE HALLWAY.
 SEE FBC TABLE 1004.
  
 NOT ADDRESSED.SEATING AREA STILL SHOWN
 IN THE HALLWAY.
  
 19.)ADDRESSED.
  
 20.)ADDRESSED.
  
 21.)ADDRESSED.
  
 22.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BATHROOMS.INCLUDE ALL
 DIMENSIONS AND SHOW CLEAR FLOOR SPACE
 FOR FIXTURES.NO DETAILS WERE PROVIDED;
 CODE COMPLIANCE CANNOT BE DETERMINED.
 SEE FBC CHAPTER 11.
  
 SHOW DISTANCE FROM CL OF WATER CLOSET TO
 THE WALL, FBC11 FIGURE 30.SHOW CLEAR
 FLOOR SPACE AND TURNING RADIUS ON THE
 FLOOR PLAN.
  
 23.)SIGNAGE FOR THE ELEVATOR IS TO BE
 COMPLIANT WITH FBC11-4.10.
  
 PLANS ARE TO SHOW CODE COMPLIANT.A
 STATEMENT THAT THE ELEVATOR CONTRACTOR
 IS RESPONSIBLE FOR SIGNAGE IS NOT
 SHOWING DESIGN CRITERIA OR CODE
 COMPLIANCE.
  
 24.)SHOW COMPLIANCE WITH FBC11-4.13.7,
 FBC FIGURE 11-26(A).
  
 NOT ADDRESSED.PROVIDE THE REQUIRED
 DIMENSION ON THE PLAN.
  
 25.)THE APPLICATION STATES THAT
 INTERIOR STAIRS ARE TO BE CLOSED OFF.
 PROVIDE A LOCATION AND A DETAIL.WILL
 IT BE CLOSED OFF BOTH UPSTAIRS AND
 DOWNSTAIRS?
  
 PLANS NOW SHOW THE DETAIL AND SCOPE OF
 WORK IS CLEAR, BUT NON COMPLIANT.
  
 26.)PLEASE NOTE THAT IT WOULD BE
 REASONABLE TO ANTICIPATE THAT A THIRD
 PLAN REVIEW WILL BE NECESSARY AS MANY
 ITEMS ARE NOT CODE COMPLIANT AND THERE
 IS INSUFFICIENT INFORMATION ON THE PLAN
 TO DEVELOP A COMPLETE CORRECTION LIST.
  
 27.)A COPY OF THE PLANS HAS BEEN
 RETAINED.
  
 A COPY OF THIS PLAN HAS ALSO BEEN
 RETAINED AND WILL BE FORWARDED TO FBPE.
  
 NEW COMMENTS:
  
 28.)A DETAIL HAS BEEN PROVIDED FOR A
 NEW SECTION OF FLOORING WHICH USES
 COMBUSTIBLE MATERIALS.THIS IS NOT
 PERMITTED IN A TYPE IV.
  
 29.)THE ENGINEER'S SEAL IS TO STATE
 "LICENSE" RATHER THAN "CERTIFICATE"
 EFFECTIVE 1/1/2006, FAC61G15-23.002(1).
  
 30.)PROVIDE INTERIOR FINISH
 CLASSIFICATION FBC TABLE 803.3.
  
 31.)PROVIDE A REASONABLE VALUE FOR THE
 SCOPE OF WORK, OR AN ESTIMATE WILL BE
 DONE FOR YOU USING MARSHALL & SWIFT.
  
 32.)WHEN RESUBMITTING, INCLUDE A
 RESPONSE LETTER ON THE ENGINEER'S
 LETTERHEAD INDICATING HOW EACH ITEM HAS
 BEEN ADDRESSED.
  
 33.)PROVIDE A COMPLETE DESCRIPTION OF
 THE ACTIVITY FOR EACH ROOM SO THAT
 OCCUPANCY AND OCCUPANT LOAD CAN BE
 PROPERLY DETERMINED.
  
 34.)PROVIDE A DETAIL FOR THE BAR TO
 COMPLY WITH ALL REQUIREMENTS OF
 FBC11-5.2.
  
 35.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS NOT PROPERLY ADDRSSED.