Plan Review Notes
Plan Review Notes For Permit 05090176
Permit Number 05090176
Review Stop P
Sequence Number 1
Notes
Date Text
2005-10-22 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW.
 DENIED
 1) SHT-1
 SECTION P403
 MINIMUM PLUMBING FACILITIES
 ?P403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED
 FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE P403.1.
 TYPES OF OCCUPANCIES NOT SHOWN IN TABLE
 P403.1 SHALL BE CONSIDERED
 INDIVIDUALLY BY THE CODE OFFICIAL.THE
 NUMBER OF OCCUPANTS SHALL BE
 DETERMINED BY THE BUILDING CODE.
 OCCUPANCY CLASSIFICATION SHALL BE
 DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2)?11-4.22 TOILET ROOMS.
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH
 ?11-4.13.DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 ?11-4.22.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.22.4, ?11-4.22.5,
 ?11-4.22.6, AND ?11-4.22.7 SHALL BE
 ON AN ACCESSIBLE ROUTE.AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH 11-4.2.3
 SHALL BE PROVIDED WITHIN AN ACCESSIBLE
 TOILET ROOM.THE CLEAR FLOOR SPACE AT
 FIXTURES AND CONTROLS, THE ACCESSIBLE
 ROUTE, AND THE TURNINGSPACE MAY
 OVERLAP.
 ?11-4.22.4 WATER CLOSETS. IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH ?11-4.17; WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION
 TO THE STALL COMPLYING WITH
 ?11-4.17.3, AT LEAST ONE STALL 36 IN
 (915 MM) WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND
 PARALLEL GRAB BARS COMPLYING WITH
 FIGURE 11-30(D) AND ?11-4.26 SHALL BE
 PROVIDED.WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH
 ?11-4.16.IF WATER CLOSETS ARE NOT IN
 STALLS, THEN AT LEAST ONE SHALL COMPLY
 WITH ?11-4.16.
 ?11-4.22.5 URINALS. IF URINALS ARE
 PROVIDED, THEN AT LEAST ONE SHALL
 COMPLY WITH ?11-4.18.
 ?11-4.22.6 LAVATORIES AND MIRRORS. IF
 LAVATORIES AND MIRRORS ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL COMPLY WITH ?11-4.19.
 ?11-4.22.7 CONTROLS AND DISPENSERS. IF
 CONTROLS, DISPENSERS, RECEPTACLES, OR
 OTHER EQUIPMENT ARE PROVIDED, THEN AT
 LEAST ONE OF EACH SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL COMPLY WITH
 ?11-4.27.
 3) PROVIDE A DETAIL SHT SHOWING
 ELEVATIONS,DIMENSIONS AND CLEAR FLOOR
 SPACE FOR ALL FIXTURES.
 END OF COMMENTS QUESTIONS 561-805-6692
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved