| Plan Review Notes For Permit 05090176 |
| Permit Number |
05090176 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-05 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SHOW THE LOCATIONS OF NEW OR | | | EXISTING 2A-10B,C RATED FIRE | | | EXTINGUISHERS THAT ARE REQUIRED. | | | | | | 2) PLEASE EXPLAIN THE SEATING AREA THAT | | | LEADS TO AN EXIT OUTSIDE THE BIRTHDAY | | | SITTING ROOM. REQUIRED MEANS OF EGRESS | | | SHALL REMAIN CLEAR AT ALL TIMES. | | | | | | 3) THE DOOR TO THE RECEPTION ROOM | | | APPEARS TO OBSTRUCT THE MEANS OF EGRESS | | | BY GREATER THAN 1/2 THE WIDTH. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|