| 2005-09-12 00:00:00 | *********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE SERVICE RISERS SHOWN |
| | INDICATE MORE THAN 6 MAINS FOR BLDG. |
| | PLEASE SEE THE TWO NEW METERS AND MAINS, |
| | SHOWN ARE NOT PERMITTED.230.2 |
| | |
| | 2)NOTE: PLEASE SEE REVIEW COMMENTS FROM |
| | OTHER TRADES WHICH WILL AFFECT |
| | ELECTRICAL PLANS. |
| | PLEASE SEE POSSIBLE CHANGE IN |
| | USE/OCCUPANCY INSTENED. |
| | |
| | 3)NOTE: PLEASE SHOW ALL NEW AND EXISTING |
| | EMERGENCY LT/ EXT LTS AND CIRCUITING PER |
| | 700.12E. THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE SEE NFPA-101 7.8 AND 7.9 |
| | WHICH WILL REQUIRE EM LT FOR EXIT |
| | DISCHARGE FROM 2ND FLR TO PUBLIC RIGHT |
| | OF WAY. |
| | |
| | 4)NOTE: PLEASE SEE A SWITCHED RECEPT IN |
| | A COMMERICAL OCCUPANCY ISNOT PERMITTED |
| | AS MEANS OF PROVIDING ILLUMINATION. |
| | PLEASE PROVIDE A LIGHTING LAYOUT OF |
| | EITHER EXISTING OR NEW FOR ALL AREAS. |
| | PLEASE ALSO SEE NEW BATH ROOMS WILL |
| | REQUIRE EM LTS. |
| | |
| | 5)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS |
| | FOR NEW LOADS ADDED TO EXSITING PANEL |
| | AND SERVICE. |
| | 215.5,220.3,220.10,.220.11,220.13 ETC |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| | SHOWN AT 125%. 215.3,230.42 |
| | |
| | 6)NOTE: PLEASE PROVIDE SIGNCIRCUIT PER |
| | 600.5 |
| | |
| | 7)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU/RTU'S.125% MIN. |
| | PLEASE ALSO INDICATE IF NEW OR EXISTING |
| | GFI'S ARE AT ROOF TOP LOCATION FOR |
| | EQUIPMENT. |
| | 210.63 |
| | |
| | PLEASE BE SURE TO SEE ALL COMMENTS FROM |
| | OTHER TRADES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |