2005-09-12 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE SERVICE RISERS SHOWN
 INDICATE MORE THAN 6 MAINS FOR BLDG.
 PLEASE SEE THE TWO NEW METERS AND MAINS,
 SHOWN ARE NOT PERMITTED.230.2
  
 2)NOTE: PLEASE SEE REVIEW COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT
 ELECTRICAL PLANS.
 PLEASE SEE POSSIBLE CHANGE IN
 USE/OCCUPANCY INSTENED.
  
 3)NOTE: PLEASE SHOW ALL NEW AND EXISTING
 EMERGENCY LT/ EXT LTS AND CIRCUITING PER
 700.12E. THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE NFPA-101 7.8 AND 7.9
 WHICH WILL REQUIRE EM LT FOR EXIT
 DISCHARGE FROM 2ND FLR TO PUBLIC RIGHT
 OF WAY.
  
 4)NOTE: PLEASE SEE A SWITCHED RECEPT IN
 A COMMERICAL OCCUPANCY ISNOT PERMITTED
 AS MEANS OF PROVIDING ILLUMINATION.
 PLEASE PROVIDE A LIGHTING LAYOUT OF
 EITHER EXISTING OR NEW FOR ALL AREAS.
 PLEASE ALSO SEE NEW BATH ROOMS WILL
 REQUIRE EM LTS.
  
 5)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS
 FOR NEW LOADS ADDED TO EXSITING PANEL
 AND SERVICE.
 215.5,220.3,220.10,.220.11,220.13 ETC
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125%. 215.3,230.42
  
 6)NOTE: PLEASE PROVIDE SIGNCIRCUIT PER
 600.5
  
 7)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU/RTU'S.125% MIN.
 PLEASE ALSO INDICATE IF NEW OR EXISTING
 GFI'S ARE AT ROOF TOP LOCATION FOR
 EQUIPMENT.
 210.63
  
 PLEASE BE SURE TO SEE ALL COMMENTS FROM
 OTHER TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  