2005-11-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THIS RENOVATION INVOLVES A CHANGE
 OF OCCUPANCY, SEE FBC106.1.1,
 FBC106.4.1.
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 THE BUILDING; TOTAL AREA, BUILDING TYPE
 FBC CHAPTER 6, PROTECTED OR UNPROTECTED,
 SPRINKLED OR UNSPRINKLED.
  
 4.)PROVIDE A PLAN SHOWING ALL TENANTS,
 FIRST FLOOR AND SECOND, WITH OCCUPANCY
 FOR EACH.
  
 5.)DECLARE AN OCCUPANCY AND
 SUBCLASSIFICATION FOR THIS IMPROVEMENT,
 SEE FBC304.
  
 6.)PROVIDE A SITE PLAN SHOWING THE
 BUILDING?S LOCATION ON THE LOT AND THE
 ACCESSIBLE ROUTE, FBC11-4.1.2.
  
 7.)DECLARE AN OCCUPANT LOAD FOR THIS
 AREA, FBC1003.1, FBC TABLE 1003.1.
  
 8.)SHOW REQUIRED OCCUPANCY AND/OR
 TENANT SEPARATIONS.PROVIDE A LISTED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC709.
  
 9.)PROVIDE A CERTIFICATION FOR THE
 FLOOR LOADING FOR THIS OCCUPANCY, FBC
 TABLE1604.1.INCLUDE THE BALCONY.
 PROVIDE DETAILS.
  
 10.)PROVIDE ELEVATIONS SO THAT CODE
 COMPLIANCE IN REGARDS TO THE LARGE
 WINDOWS AND THE EXIT STAIR CAN BE
 DETERMINED.
  
 11.)SEE FBC2405.IS SAFETY GLASS
 REQUIRED?
  
 12.)PROVIDE A LIFE SAFETY PLAN.SHOW
 ALL EXIT LIGHTS.NOT ENOUGH INFORMATION
 WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.PLEASE REACH FBC CHAPTER 10
 AND SHOW COMPLIANCE ON THE PLAN.SEE
 ALSO FBC11-4.1.3(9).
  
 13.)PROVIDE DETAILS AND DESIGN
 CRITERIA FOR BOTH STAIRS AND THE HAND
 RAILS AND STAIR GUARDRAILS, FBC1007 ,
 FBC11-4.9,FBC1015, FBC1608,
 FBC11-4.26.
  
 14.)PROVIDE A DETAIL AND DESIGN
 CRITERIA FOR THE BALCONY GUARDRAIL.
 FBC1007, FBC1608.
  
 15.)FIRE RATING IS NOT SHOWN BETWEEN
 THE HALL AND THE RECEPTION AREA.THIS
 APPEARS TO BE COMMON AREA, SEPARATION
 REQUIRED.
  
 16.)IF THE WALL BETWEEN THE RECEPTION
 AND HALL IS TO BE RATED, A FIRE RATED
 DOOR REQUIRED FBC TABLE 705.1.2.
  
 17.)IF THIS BUILDING IS NOT FULLY
 SPRINKLED, AREA OF RESCUE ASSISTANCE
 REQUIRED, FBC11-4.1.3(9).IF THIS
 BUILDING IS FULLY SPRINKLED, INDICATE
 AND PROVIDE A SPRINKLER PLAN.
  
 18.)THE SEATING AREA BLOCKS THE
 REQUIRED EGRESS WIDTH OF THE HALLWAY.
 SEE FBC TABLE 1004.
  
 19.)THE DOORS FROM THE RECEPTION TO
 HALLWAYS DO NOT COMPLY WITH FBC1012.1.4.
  
  
 20.)PROVIDE A DIMENSION FOR THE
 BALCONY.THE DOORS TO THE BALCONY ARE
 TO COMPLY WITH FBC1012.1.4.
  
 21.)THE DOORS MARKED DOOR 1 OR DOOR 2
 DO NOT MEET THE REQUIREMENTS OF
 FBC11-4.13.5.
  
 22.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BATHROOMS.INCLUDE ALL
 DIMENSIONS AND SHOW CLEAR FLOOR SPACE
 FOR FIXTURES.NO DETAILS WERE PROVIDED;
 CODE COMPLIANCE CANNOT BE DETERMINED.
 SEE FBC CHAPTER 11.
  
 23.)SIGNAGE FOR THE ELEVATOR IS TO BE
 COMPLIANT WITH FBC11-4.10.
  
 24.)SHOW COMPLIANCE WITH FBC11-4.13.7,
 FBC FIGURE 11-26(A).
  
 25.)THE APPLICATION STATES THAT
 INTERIOR STAIRS ARE TO BE CLOSED OFF.
 PROVIDE A LOCATION AND A DETAIL.WILL
 IT BE CLOSED OFF BOTH UPSTAIRS AND
 DOWNSTAIRS?
  
 26.)PLEASE NOTE THAT IT WOULD BE
 REASONABLE TO ANTICIPATE THAT A THIRD
 PLAN REVIEW WILL BE NECESSARY AS MANY
 ITEMS ARE NOT CODE COMPLIANT AND THERE
 IS INSUFFICIENT INFORMATION ON THE PLAN
 TO DEVELOP A COMPLETE CORRECTION LIST.
  
 27.)A COPY OF THE PLANS HAS BEEN
 RETAINED.