| 2005-11-06 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)THIS RENOVATION INVOLVES A CHANGE |
| | OF OCCUPANCY, SEE FBC106.1.1, |
| | FBC106.4.1. |
| | |
| | 3.)PROVIDE INFORMATION IN REGARDS TO |
| | THE BUILDING; TOTAL AREA, BUILDING TYPE |
| | FBC CHAPTER 6, PROTECTED OR UNPROTECTED, |
| | SPRINKLED OR UNSPRINKLED. |
| | |
| | 4.)PROVIDE A PLAN SHOWING ALL TENANTS, |
| | FIRST FLOOR AND SECOND, WITH OCCUPANCY |
| | FOR EACH. |
| | |
| | 5.)DECLARE AN OCCUPANCY AND |
| | SUBCLASSIFICATION FOR THIS IMPROVEMENT, |
| | SEE FBC304. |
| | |
| | 6.)PROVIDE A SITE PLAN SHOWING THE |
| | BUILDING?S LOCATION ON THE LOT AND THE |
| | ACCESSIBLE ROUTE, FBC11-4.1.2. |
| | |
| | 7.)DECLARE AN OCCUPANT LOAD FOR THIS |
| | AREA, FBC1003.1, FBC TABLE 1003.1. |
| | |
| | 8.)SHOW REQUIRED OCCUPANCY AND/OR |
| | TENANT SEPARATIONS.PROVIDE A LISTED |
| | ASSEMBLY OR CALCULATED FIRE RESISTANCE |
| | FBC709. |
| | |
| | 9.)PROVIDE A CERTIFICATION FOR THE |
| | FLOOR LOADING FOR THIS OCCUPANCY, FBC |
| | TABLE1604.1.INCLUDE THE BALCONY. |
| | PROVIDE DETAILS. |
| | |
| | 10.)PROVIDE ELEVATIONS SO THAT CODE |
| | COMPLIANCE IN REGARDS TO THE LARGE |
| | WINDOWS AND THE EXIT STAIR CAN BE |
| | DETERMINED. |
| | |
| | 11.)SEE FBC2405.IS SAFETY GLASS |
| | REQUIRED? |
| | |
| | 12.)PROVIDE A LIFE SAFETY PLAN.SHOW |
| | ALL EXIT LIGHTS.NOT ENOUGH INFORMATION |
| | WAS PROVIDED TO DETERMINE CODE |
| | COMPLIANCE.PLEASE REACH FBC CHAPTER 10 |
| | AND SHOW COMPLIANCE ON THE PLAN.SEE |
| | ALSO FBC11-4.1.3(9). |
| | |
| | 13.)PROVIDE DETAILS AND DESIGN |
| | CRITERIA FOR BOTH STAIRS AND THE HAND |
| | RAILS AND STAIR GUARDRAILS, FBC1007 , |
| | FBC11-4.9,FBC1015, FBC1608, |
| | FBC11-4.26. |
| | |
| | 14.)PROVIDE A DETAIL AND DESIGN |
| | CRITERIA FOR THE BALCONY GUARDRAIL. |
| | FBC1007, FBC1608. |
| | |
| | 15.)FIRE RATING IS NOT SHOWN BETWEEN |
| | THE HALL AND THE RECEPTION AREA.THIS |
| | APPEARS TO BE COMMON AREA, SEPARATION |
| | REQUIRED. |
| | |
| | 16.)IF THE WALL BETWEEN THE RECEPTION |
| | AND HALL IS TO BE RATED, A FIRE RATED |
| | DOOR REQUIRED FBC TABLE 705.1.2. |
| | |
| | 17.)IF THIS BUILDING IS NOT FULLY |
| | SPRINKLED, AREA OF RESCUE ASSISTANCE |
| | REQUIRED, FBC11-4.1.3(9).IF THIS |
| | BUILDING IS FULLY SPRINKLED, INDICATE |
| | AND PROVIDE A SPRINKLER PLAN. |
| | |
| | 18.)THE SEATING AREA BLOCKS THE |
| | REQUIRED EGRESS WIDTH OF THE HALLWAY. |
| | SEE FBC TABLE 1004. |
| | |
| | 19.)THE DOORS FROM THE RECEPTION TO |
| | HALLWAYS DO NOT COMPLY WITH FBC1012.1.4. |
| | |
| | |
| | 20.)PROVIDE A DIMENSION FOR THE |
| | BALCONY.THE DOORS TO THE BALCONY ARE |
| | TO COMPLY WITH FBC1012.1.4. |
| | |
| | 21.)THE DOORS MARKED DOOR 1 OR DOOR 2 |
| | DO NOT MEET THE REQUIREMENTS OF |
| | FBC11-4.13.5. |
| | |
| | 22.)PROVIDE A DETAIL FOR THE |
| | ACCESSIBLE BATHROOMS.INCLUDE ALL |
| | DIMENSIONS AND SHOW CLEAR FLOOR SPACE |
| | FOR FIXTURES.NO DETAILS WERE PROVIDED; |
| | CODE COMPLIANCE CANNOT BE DETERMINED. |
| | SEE FBC CHAPTER 11. |
| | |
| | 23.)SIGNAGE FOR THE ELEVATOR IS TO BE |
| | COMPLIANT WITH FBC11-4.10. |
| | |
| | 24.)SHOW COMPLIANCE WITH FBC11-4.13.7, |
| | FBC FIGURE 11-26(A). |
| | |
| | 25.)THE APPLICATION STATES THAT |
| | INTERIOR STAIRS ARE TO BE CLOSED OFF. |
| | PROVIDE A LOCATION AND A DETAIL.WILL |
| | IT BE CLOSED OFF BOTH UPSTAIRS AND |
| | DOWNSTAIRS? |
| | |
| | 26.)PLEASE NOTE THAT IT WOULD BE |
| | REASONABLE TO ANTICIPATE THAT A THIRD |
| | PLAN REVIEW WILL BE NECESSARY AS MANY |
| | ITEMS ARE NOT CODE COMPLIANT AND THERE |
| | IS INSUFFICIENT INFORMATION ON THE PLAN |
| | TO DEVELOP A COMPLETE CORRECTION LIST. |
| | |
| | 27.)A COPY OF THE PLANS HAS BEEN |
| | RETAINED. |