| 2006-05-16 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE |
| | COMMENT #1 FROM REVIEW DATED 10/18/05: |
| | RESPONSE INDICATES NO EXHAUST DUCT |
| | EXTENDS OR PASS THROUGH RETURN AIR |
| | PLENUM.RESPONSE REFERS TO NOTE #8. |
| | NOTE #8 REFERS TO THE CITY OF BOYNTON |
| | BEACH.SEE ALSO NEW COMMENT # BELOW. |
| | |
| | COMMENT #2:OK |
| | COMMENT #3:RESPONSE TO COMMENT |
| | INDICATES RELIEF LOUVERS HAVE BEEN |
| | RELOCATED.SEE REV 1 ON PLAN SHEETS |
| | M4.4 & M4.5.PLANS STILL SHOW INTAKES |
| | AND EXHAUST TERMINATING AT AN EXIT |
| | ACCESS CORRIDOR WHICH IS PROHIBITED PER |
| | 2001 FBC 1005.3.2. |
| | |
| | COMMENT #4:OK |
| | COMMENT #5:OK |
| | COMMENT #6:OK |
| | |
| | **************************************** |
| | NEW COMMENTS: |
| | 7.PLAN SHEET M5.1 DETAIL FOR THE DRYER |
| | SHAFT.PLEASE ADDRESS THE FOLLOWING |
| | WITH REGARDS TO THE SHAFT ENCLOSURE. |
| | A) PER 2001 FBC 705.2.3.3, SHAFT SHALL |
| | CONTINUE THROUGH TO THE FIRST FLOOR. SEE |
| | ALSO EXCEPTION 1 TO THE AFOREMENTIONED |
| | CODE. |
| | |
| | 8.FIRE DAMPER SHALL NOT BE INSTALLED |
| | ON THE DRYER EXHAUST.PLEASE PROVIDE |
| | MANUFACTURER'S SPECIFICATION AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 9.AIR MAKE-UP IS NOT REQUIRED FOR THE |
| | THE SUB-DUCT SHAFT. |
| | |