| Date |
Text |
| 2006-05-23 00:00:00 | ***DENIED*** |
| | |
| | PLEASE ADDRESS SOME PREVIOUS COMMENTS IN |
| | ADDITION TO NEW COMMENTS: |
| | |
| | 1) PREVIOUS COMMENT #1- PLEASE INDICATE |
| | THE INTERIOR FINISH CLASSIFICATION THAT |
| | IS SPECIFIC TO THIS PROJECT. YOUR |
| | RESPONSE GENERALLY CITES THE TECHNICAL |
| | CODE REQUIREMENT. |
| | |
| | 2) KEY TURN ACTIVATION KNOX BOX ENTRY |
| | SYSTEM IS REQUIRED ON NEW PROPERTY ENTRY |
| | INSTALLATIONS. |
| | |
| | 3) PLEASE ILLUSTRATE ARRANGEMENT OF |
| | MEANS OF EGRESS, (TRAVEL DISTANCE TO |
| | EXITS, COMMON PATH OF TRAVEL, ETC) BASED |
| | ON TYPE OF OCCUPANCY ON LIFE SAFETY |
| | DRAWINGS. |
| | |
| | 4) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES (3) STORIES OR |
| | (30) FEET IN HEIGHT. |
| | |
| | 5) KNOX BOXES ARE REQUIRED ON THE |
| | BUILDINGS. |
| | |
| | 6) DUCT SMOKE DETECTORS SHALL INITIATE A |
| | GENERAL FIRE ALARM WHEN ACTIVATED IN |
| | ACCORDANCE WITH LOCAL REQUIREMENTS. |
| | |
| | 7) NO SMOKE DETECTORS ARE SHOWN IN |
| | CORRIDORS. PLEASE SEE NFPA 101, SECTIONS |
| | 9.6.2.8 AND 9.6.2.9 REGARDING |
| | REQUIREMENTS FOR ALL OCCUPIABLE AREAS, |
| | COMMON AREAS, CORRIDORS ETC. |
| | |
| | 8) FDV'S TO BE 2 1/2" TO 1 1/2" REDUCER |
| | WITH CHAINS. |
| | |
| | 9) DOUBLE CHECK DETECTOR ASSEMBLY SHALL |
| | IN ADDITION TO ELECTRONIC SUPERVISION, |
| | BE SECURED WITH CHAIN AND LOCK. |
| | |
| | 10) PLEASE PROVIDE PRESCRIPTIVE SRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |