| Date |
Text |
| 2006-04-17 00:00:00 | **** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH STILL NEED TO BE |
| | ADDRESSED AND SOME NEW COMMENTS DUE TO |
| | INFORMATION/OR CHANGES TO PLANS. |
| | |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW ABD NOTED. |
| | PLEASE SEE NEW NOTES WERE ADDED TO THE |
| | BOTTOM OF NOTES AND ARE NOTED AS NEW. |
| | |
| | MARVILLA |
| | |
| | 4-STORY CONDO BLDGS W/ PARKING GARAGES. |
| | |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: NO/YES, PLEASE SEE A DETAIL WAS |
| | SUBMITTED, HOWEVER PLEASE KNOW THE |
| | CURBING SHALL GO COMPLETELY AROUND BUS |
| | PENTRATING THE FLR. CAN NOT BE THREE |
| | SIDED UP ON WALL. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE A DETAIL FOR CURBING |
| | REQUIRED AROUND BUS-DUCT ON FLOOR |
| | PENETRATIONS WHERE A VERTICAL RISER |
| | PENETRATES TWO OR MORE DRY FLOORS, |
| | A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL |
| | BE INSTALLED AROUND ALL FLOOR OPENINGS |
| | FOR RISER BUSWAYS TO PREVENT LIQUIDS |
| | FROM ENTERING THE OPENING. PER 368.6 |
| | |
| | 3)NOTE: OK, HOWEVER SEE NOTE #7 FOR |
| | OTHER AREAS WHICH REQUIRE A BATTERY FIX. |
| | |
| | |
| | 4)NOTE:NO, PLEASE SEE STAIR AREA WERE |
| | NOT SHOWN AND PHOTO METRICS WERE DONE |
| | FOR MOST FLRS AND AREAS BUT NOT ALL. |
| | PLEASE SEE IF FIRST FLR IS "TYPICAL" |
| | THEN PLEASE NOTE AS: |
| | PLEASE SEE WHAT APPEARS TO BE FT CANDLES |
| | SHOWN ON OTHER SHEETS WHICH ARE NOT |
| | VISABLE. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE PROVIDE PHOTOMETRICS FOR |
| | STAIR/CORRIDOR AREAS FOR EGRESS TO THE |
| | PUBLIC RIGHT OF WAY. PLEASE SEE 2003 |
| | 101, 7.8 AND 7.9, WHICH REQUIRES 10FT |
| | CANDLES FOR STAIR AREAS AND 1FT FOR |
| | CORRIDOR. |
| | 7.8.1.3,7.9.2.1 |
| | |
| | 5)NOTE: OK. |
| | |
| | 6)NOTE:NO, PLEASE SEE RESPONSE |
| | MENTTIONS THIS TO BE DONE LATER, HOWEVER |
| | THIS IS REQUIRED AT THIS TIME AS NOTED |
| | PREVIOUSLY. THIS WOULD MOST LIKELY NOT |
| | BE DONE BY THE ELECTRICAL ENGINEER. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE DETAIL FOR ROOF TOP LT |
| | POLES AND FIXTURES. PLEASE PROVIDE WIND |
| | LOAD CALCULATIONS FOR REVIEW. THIS IS |
| | REQUIRED AT THIS TIME FOR FIXTURES AND |
| | POLES. |
| | CALCULATIONS WILL BE REVIEWED BY THE |
| | BLDG REVIEWER FOR CODE COMPLIANCE OF FBC |
| | 140 MPH WIND LOADS. |
| | |
| | 7)NOTE: NO, PLEASE SEE SOME SHEETS |
| | INDICATE THE CORRECT FIXTURE |
| | IDENTIFICATION AND CORRELATES WITH THE |
| | FIXTURE SCHEDULE, HOWEVER SOME OF THE |
| | COMMON AREA/GARAGE AREA PLANS/SHEETS |
| | SHOW FIXTURES WHICH ARE NOT BATTERY BACK |
| | UP AND /OR ARE NOT ON FIXTURE SCHEDULE |
| | AND SYMBOL SEEMS TO LEND TO THE FIXTURE |
| | BEING A BATTERY BACK UP FIXTURE OF SOME |
| | SORT. "B" , B2". |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT A COMPLETED LIGHTING |
| | FIXTURE SCHEDULE TO CORRELATE WITH |
| | FIXTURES AS SHOWN ON PLANS. PLEASE ALSO |
| | SEE COMMON AREAS WHERE FIXTURES DO NOT |
| | INDICATE WHAT TYPE ETC. |
| | RECREATION AREA, ROOF TOP ETC. |
| | |
| | 8)NOTE: OK |
| | |
| | 9)NOTE: OK. |
| | |
| | |
| | 10)NOTE: OK. |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE: OK. |
| | |
| | 13)NOTE: OK. |
| | |
| | 14)NOTE:OK, HOWEVER PLEASE CORRELATE |
| | CIRCUITING AS, UNITS SHOWN DINING ARE |
| | WITH 15A CIRCUIT(S). PLEASE SEE |
| | 210.52B1, 210.11C1 AND 220.16A FOR TWO |
| | OR MORE CIRCUITS. PLEASE ADJUST |
| | CIRCUITING ANDLOAD CALCUALTIONS. |
| | |
| | ** PRWEVIOUS NOTE ** |
| | PLEASE PROVIDE "DINING RM/AREA" |
| | DESIGNATIONS ON UNITS "A" AND "E". |
| | 210.52B. |
| | |
| | 15)NOTE: NO, PLEASE SEE SOME OF THESE |
| | RMS, ELEV EQUIPMENT ETC DO NOT SHOW ROOM |
| | DESIGNATIONS OR NOTE WHERE TO FIND. SEE |
| | GARAGE PLANS ALSO. POOL RM LABLED.OK |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE ROOM/ AREA DESIGNATIONS |
| | ON COMMON AREAS PLANS. |
| | PLEASE SEE ROOMS ETC NOT LABLED. |
| | PLEASE SEE ELECTRICAL PLANS DO NOT |
| | INDICATE "POOL EQUIPMENT " ROOM ETC. |
| | |
| | 16)NOTE:NO, SAME NOTE:RESPONSE |
| | MENTIONS TO SEE REVISED SHEETS, HOWEVER |
| | THE SAME #'S ARE SHOWNA S ON PREVIOUS |
| | PLANS.?? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 424.3B WHICH REQUIRES ALL |
| | OVERCURRENT PROTECTION FOR AHU'S HEAT TO |
| | BE A MIN OF 125%. |
| | PLEASE SEE THESE AS REDLINED ON PLANS. |
| | PLEASE ALSO REVISE MIN AWG PER 310.16 |
| | ONCE OCP HAS BEEN ADJUSTED. |
| | PLEASE KNOW, MOST OCP IS 150% MAX, |
| | HOWEVER WHEN A AMPERAGE DOES NOT |
| | CORRESPONED TO A COMMON OCP DEVICE AS |
| | LISTED IN 240.6, GOING UP TO THE NEXT |
| | HIGHER OCP IS PERMITTED. |
| | |
| | 17)NOTE:NO, SAME NOTE,RESPONSE |
| | MENTIONS TO SEE REVISED, HOWEVER THE |
| | PANEL SCHEDULES WERE NOT CHANGED?? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE MANY OF THE UNITS AS LISTED |
| | ON HOUSE PANELS ALSO NEED TO BE |
| | ADJUSTED. |
| | PLEASE SEE L2B AHU#10, SHOWS 11KW ON A |
| | 2P-30A WITH #10 AWG. |
| | AHU #11 LISTED TWICE, SHOWS 11KW ON |
| | 2P-45A WITH #8. |
| | AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A |
| | OCP THIS ONE IS OK. |
| | PLEASE SEE AHU#10 IS LISTED TWICE ALSO. |
| | PLEASE SEE AHU #6 ON LRB. |
| | PLEASE SEE AHU #7 ON LRB. |
| | BOTH WITH THE SAME COMMENTS AS LISTED |
| | ABOVE. |
| | PLEASE ADJUST.424.3B,310.16 |
| | |
| | 18)NOTE: NO,?? RESPONSE LTR MENTIONS TO |
| | SEE REVISED,HOWVER THE SAME #'S ARE |
| | SHOWN? |
| | ** PREVIOUS NOTES** |
| | PLEASE SEE MIN OCPFOR WATER HEATER |
| | UNITS, SHALL BE A MIN OF 125% AND A MAX |
| | OF 150%. |
| | PLEASE SEE 6KW SHOWN ON A 2P35. |
| | 422.13,422.11E3 |
| | |
| | 19)NOTE: OK, HOWEVER PLEASE SEE THE |
| | CONTINUOUS LOADS NOTE WAS ADDED TO ALL |
| | PLANS INCLUDING UNITS?? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. PLEASE SEE THIS IS FOR LOADS |
| | DEDICATED TO HOUSE PANELS, POOL PUMPS, |
| | ANY POOL HEAT PUMPS, LIGHTING , LARGEST |
| | MOTOR STEC. |
| | 215.3,230.42 ETC. |
| | |
| | 20)NOTE: OK. |
| | |
| | 21)NOTE: OK/NO, PLEASE SEE SPECS WERE |
| | SUBMITTED AND VERIFIED, HOWEVER PLEASE |
| | SEE PLANS DO NOT REFLECT OR NOTE |
| | ANYTHING FOR LOCKED ROTOR FOR THE FIRE |
| | PUMP AND PLANS AND SPECS FOR THE FIRE |
| | PUMP DO NOT CORRELATE FOR SIZING. PLEASE |
| | SPECIFY THE LOCAKED ROTOR SETTING PER |
| | MANUFACTURES SPECS AND PLEASE CORRELATE |
| | THE HP RATINGS. (SPECS SHOW 100HP AND |
| | RISER SHOWS 125HP).REVIEW FOR CONDUCTORS |
| | OCP ETC CANNOT BE DONE AT THIS TIME. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT |
| | SHEETS FOR FIRE PUMP AND FIRE PUMP |
| | CONTROLLER. |
| | PLEASE BE SURE NOTES FOR LOCKED ROTOR |
| | AND MANUAL MEANS OF DISCONNECT IS |
| | LOCATED ON PLANS. |
| | PLEASE SEE 695.4B1, |
| | NFPA-20 10.4.2.1.1,10.4.2.2 ETC. |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | AT THIS TIME EVEN IF FIRE PUMP/ |
| | CONTROLLER IS PERMITTED UNDER FIRE |
| | SPRINKLER PERMIT. |
| | |
| | 22)NOTE:OK. |
| | |
| | 23)NOTE: OK. |
| | |
| | 24)NOTE: OK. |
| | |
| | 25)NOTE: OK. |
| | |
| | 26)NOTE: OK. |
| | |
| | 27)NOTE: OK. |
| | |
| | 28)NOTE: OK. |
| | |
| | 29)NOTE: OK. |
| | |
| | 30)NOTE:OK, HOWEVER PLEASE SEE COMMON |
| | AREA PLANS AND GARAGE LIGHTING PLANS |
| | WHICH INDICATE THE LIGHTING IN THESE RMS |
| | CIRCUITED TO THE GARAGE LTS. |
| | PLEASE ADJUST. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 620.23,620.24 WHICH REQUIRES |
| | DEDICATED CIRCUITS FOR ELEVATOR PIT LTS |
| | AND RECEPTS. THIS CIRCUIT MAY NOT FEED |
| | ANY OTHER LTS AND RECEPTS. |
| | THESE SHALL ALSO BE DEDICATE TO EACH |
| | ELEVATOR/PIT. |
| | PLEASE SEE CIRCUITS FOR ELEVATOR |
| | EQUIPMENT ROOMS SHALL ALSO BE DEDICATED |
| | AND MAY NOT FEED ANY OTHER ROOMS OR |
| | ELECTRICAL LIGHTING OR RECEPTS. |
| | PLEASE ALSO SEE PREVIOUS NOTE WHICH IS |
| | REQUIRING A BATTERY BACK-UP FIXTURE IN |
| | THESE ROOMS. |
| | PLEASE ALSO SEE 700.16D |
| | |
| | 31)NOTE: OK. |
| | |
| | 32)NOTE: OK. |
| | |
| | 33)NOTE: OK. |
| | |
| | |
| | ****** NEW NOTE **** |
| | |
| | 34) NOTE: PLEASE SEE ALL UNITS LOCATED |
| | ON THE FIRST FLR WITH GRADE LEVEL |
| | ACCESS/EGRESS FROM UNIT/ FROM PATIO |
| | SHALL CONTAIN A LT FIXTURE OF SOME SORT |
| | FOR EGRESS LT. THIS MAY BE ADDRESSED AS |
| | A CLOUDED NOTE FOR ALL FIRST FLR UNITS. |
| | 210.70, LS 101-7.8 |
| | |
| | 35) NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | REPEAT COMMENTS. THIS IS ONLY A NOTICE |
| | AT THIS TIME. |
| | |
| | ** PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| | HAVE BEENREDLINED ON PLANS FOR AREAS |
| | OF COMMENTS. |
| | |
| | **PLEASE SEE ALL COMMENTS FROM ALL OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE SEE FIRE REVIEW COMMENTS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE SET OF ALL OL/VOIDED |
| | SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DONOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-04-13 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW |