| 2006-05-22 00:00:00 | PERMIT NUMBER: 05090156 |
| | ADDRESS: 3701 N MILITARY TRAIL |
| | CONTRACTOR: TOWN AND COUNTRY HOMES |
| | FOUR STORY R2 WITH PARKING GARAGE |
| | TYPE II SPRINKLERED (13R SYSTEM) |
| | CODE EDITION: 2001 FBC |
| | SECOND REVIEW |
| | --------------------------------------- |
| | DENIED |
| | |
| | |
| | 1)WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 2) CONDOMINIUM V APARTMENTS.IF THE |
| | DWELLING UNITS ARE TO BE SOLD AS |
| | CONDOMINIUMS, A 'DECLARATION OF |
| | CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| | STATE FOR APPROVAL, AND THEN RECORDED |
| | WITH THE CLERK OF THE COUNTY COURT.A |
| | RECORDED COPY SHALL BE SUBMITTED TO THE |
| | CITY FOR RECORDS, ADDRESSING PURPOSES, |
| | AND TO PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S OFFICE PRIOR TO C.O. |
| | RECORDED COPY OF CONDOMINIUM DOCUMENTS |
| | RECEIVED. |
| | |
| | 3) ALL THREE (3) COPIES OF THE |
| | SUBSURFACE SOIL REPORTS, OTHER REPORTS, |
| | CALCULATIONS AND DRAWINGS PREPARED BY A |
| | FLORIDA REGISTERED ARCHITECT OR ENGINEER |
| | ARE REQUIRED TO BE SIGNED AND SEALED. |
| | |
| | 4) SUBMIT (3) SETS OF ENGINEERED LAYOUTS |
| | AND TRUSS DRAWINGS FOR THE METAL TRUSSES |
| | THAT HAVE BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. |
| | |
| | 5) REVISED DETAILS #9 THRU #13 ON SHEET |
| | A-8.3.1 AND #2, #4 ON A-8.3.2 SPECIFY |
| | WOOD TRUSSES AND DO NOT SPECIFY FIRE |
| | TREATED PLYWOOD. THIS STRUCTURE IS |
| | SPECIFIED AS TYPE II CONSTRUCTION AND |
| | DOES NOT ALLOW COMBUSTIBLE MATERIALS AT |
| | THIS LOCATION. PLEASE CORRECT. |
| | |
| | 6) SPECIFY THE ATTACHMENT SPACING AND |
| | FASTENERS FOR THE FIRETREATED PLYWOOD |
| | SHEATHING TO THE METAL TRUSSES. |
| | |
| | 7) SUBMIT (3) SETS OF ENGINEERED SHOP |
| | DRAWINGS AND LAYOUTS FOR THE PRECAST |
| | SYSTEM FOR THE PARKING GARAGE.(PRIOR TO |
| | CONSTRUCTION) |
| | |
| | 8) THE CORRIDOR BETWEEN THE FITNESS |
| | CENTER AND THE BATH ROOMS IS A DEAD END |
| | HALLWAY THAT EXCEEDS TWENTY FEET IN |
| | LENGTH WHICH IS PROHIBITED BY FBC |
| | 1005.2. |
| | |
| | 9) 2001 FBC 903.7.6 REQUIRES GROUP R2 |
| | OCCUPANCIES THREE OR MORE STORIES IN |
| | HEIGHT TO BE PROVIDED THROUGHOUT WITH AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM. |
| | EXCEPTION (2) ALLOWS AN AUTOMATIC |
| | SPRINKLER SYSTEM COMPLYING WITH NFPA 13R |
| | FOR BUILDINGS NOT EXCEEDING FOUR STORIES |
| | IN HEIGHT PROVIDED THE AUTOMATIC |
| | SPRINKLER SYSTEM SHALL NOT BE CONSIDERED |
| | AS AN ALTERNATE TO OTHER REQUIREMENTS OF |
| | THE CODE. (SEE 903.2) FBC 903.2 STATES |
| | THAT AUTOMATIC SPRINKLER SYSTEMS |
| | INSTALLED IN LIEU OF OR AS AN ALTERNATE |
| | TO OTHER REQUIREMENTS, AS PERMITTED BY |
| | THIS CODE, SHALL BE CONSIDERED REQUIRED |
| | SYSTEMS AND SHALL COMPLY WITH NFPA 13. |
| | THIS MEANS THAT IN ORDER TO APPLY THE |
| | REDUCTION IN CORRIDOR FIRE RATING |
| | ALLOWED BY TABLE 704.2.4 TO 1/2 HOUR FOR |
| | FULLY SPRINKLERED BUILDINGS OR THE |
| | INCREASED TRAVEL DISTANCE OF 325' IN |
| | TABLE 1004 FOR SPRINKLERED BUILDINGS AN |
| | NFPA 13 SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | 10) THE BILLARD ROOM IS AN ASSEMBLY |
| | OCCUPANCY WHICH REQUIRES A TWO HOUR |
| | TENANT FIRE SEPARATION. SEE FBC 704.1.1 |
| | HOWEVER, FBC 704.1.2.3 ALLOWS A ONE HOUR |
| | OCCUPANCY SEPARATION. |
| | |
| | 11) ALL FIRE RATED DOORS ARE REQUIRED TO |
| | HAVE APPROVED CLOSERS OR BE SELF |
| | CLOSING. SPECIFY CLOSERS FOR ALL RATED |
| | DOORS PER FBC 705.1.3.2.3. SPECIFY IN |
| | THE DOOR SCHEDULE ON A4.0.8 THAT DOOR #4 |
| | IS REQUIRED TO HAVE APPROVED CLOSERS. |
| | |
| | 12) A VERTICAL SECTION THROUGH THE TRASH |
| | CHUTE IS INDICATED AS 5 ON A4.0.10 THIS |
| | IS INCORRECT AS IT IS LOCATED ON DETAIL |
| | 5 ON A4.0.10. PLEASE CORRECT. |
| | |
| | 13) THE TRASH CHUTE SECTION SHOWN ON |
| | SHEET A8.1.4 IS INCORRECTLY LABELED AS 4 |
| | ON A4.0.7. PLEASE CORRECT. |
| | |
| | 14) PLEASE REVISE NEW NOTES ON A8.2.1 |
| | AND A8.2.2 WHICH REFER TO THE HIGH |
| | VELOCITY HURRICANE ZONES AS REQUIRING |
| | IMPACT PROTECTION. THE CITY OF WEST PALM |
| | BEACH IS NOT IN THE HIGH VELOCITY |
| | HURRICANE ZONE, HOWEVER, WE ARE LOCATED |
| | IN THE WIND BOURNE DEBRIS REGION AND |
| | BECAUSE OF THIS MISSILE IMPACT |
| | PROTECTION OF EXTERIOR GLAZING IS |
| | REQUIRED. SEE 2001 FBC 1606.1.4. |
| | |
| | 15) SUBMIT THE MANUFACTURER'S |
| | SPECS.(LISTING) AND PRODUCT APPROVALS |
| | FOR THE FIRE RATED GLASS BLOCK. |
| | |
| | 16) THE INTERNAL PRESSURE COEFFICENT ON |
| | SHEET S7 IS POSITIVE AND NEGATIVE + OR |
| | -0.18. PLEASE CORRECT. |
| | |
| | 17) MANY OF THE FULL LOUVERED DOORS ARE |
| | LOCATED IN FIRE RATED WALLS AND OPEN |
| | ONTO THE EGRESS CORRIDORS. THESE DOORS |
| | ARE REQUIRED TO BE FIRE RATED. I DO NOT |
| | BELIEVE THAT THERE ARE ANY FIRE RATED |
| | FULL LOUVERED DOORS AVAILABLE. SUBMIT |
| | MANUFACTURER'S SPECS. AND LISTING FOR |
| | THE DOORS YOU WILL BE USING. |
| | |
| | 18) THE PRODCUCT APPROVALS SUBMITTED FOR |
| | THE FULL LOUVERED DOORS REQUIRES A |
| | HURRICANE PROTECTION SYSTEM FOR THEM. |
| | SUBMIT A STATE PRODUCT APPROVAL, A KEY |
| | PLAN, AN INSTALLATION SCHEDULE AND A |
| | PRESTORM PREPARATION PLAN FOR BUILDING |
| | OFFICAL APPROVAL FOR THE STORM PANELS |
| | FOR THESE DOORS. |
| | |
| | 19) SPECIFY THE LOCATIONS WHERE THE |
| | THERMA-TRU/ BENCHMARK DOORS WILL BE |
| | INSTALLED. THESE DOORS DO NOT HAVE A |
| | FIRE RATING. |
| | |
| | 20) SUBMIT STATE PRODUCT APPROVALS FOR |
| | THE ROOFING MATERIAL THAT WILL BE USED |
| | ON THE FLAT ROOF AREAS OF THE BUILDING. |
| | INDICATE THE SYSTEM LISTED IN THE |
| | PRODUCT APPROVAL THAT WILL BE USED. MAKE |
| | SURE THAT THE DESIGN PRESSURES FOR THE |
| | SELECTED PRODUCT ARE ADEQUATE. |
| | |
| | 21) THE WINDOWS (E) LOCATED IN THE ONE |
| | HOUR FIRE RATED PARTIONS ON SHEET A4.0.8 |
| | ARE REQUIRED TO BE 45 MIN. FIRE |
| | PROTECTION RATED PER FBC 705.1.3.6.2. |
| | THE SCHEDULE LISTS 20 MIN. RATED. PLEASE |
| | CORRECT. |
| | |
| | 22)A SEPARATE PERMIT WILL BE REQUIRED |
| | FOR SITE AMENITIES. A SITE PLAN SHOWING |
| | ACCESSIBLE ROUTES TO ALL BUILDINGS, |
| | AMENITIES, PARKING AND TO THE PUBLIC WAY |
| | AS REQUIRED BY FBC 11-4.1.2, THE FAIR |
| | HOUSING ACCESSIBILITY GUIDELINES AND |
| | ANSI 4.3. SHOW CURB RAMPS, SIDE WALK |
| | WIDTHS, SIGNAGE, DETECTABLE WARNINGS, |
| | CROSSWALKS,ETC. DETAILS OF THE COMMON |
| | TRASH PICK-UP AREA, GAZEBOS AND TOT LOT |
| | MUST SHOW COMPLIANCE WITH ADA |
| | REQUIREMENTS. |
| | |
| | 23) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 24) ADDITIONAL COMMENTS MAY RESULT FROM |
| | RESPONSES TO THESE ISSUES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |