| Date |
Text |
| 2005-10-04 00:00:00 | MARVILLA |
| | |
| | 4-STORY CONDO BLDGS W/ PARKING GARAGES. |
| | |
| | *********** UNSAT ********** |
| | |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE TO |
| | REFERENCE THE 2002 NEC AS ADOPTED BY THE |
| | STATE OF FLORIDA.(JULY 1ST, 2003) |
| | PLEASE ALSO SEE NOTES FOR PLANS WHICH |
| | INDICATE LOCAL AMENDMENTS PER CITY OF |
| | BOYNTON BEACH. PLEASE SEE NOTE WOULD |
| | REFERENCE LOCAL AMENDMENTS PER CITY OF |
| | WEST PALM BEACH. |
| | |
| | 2)NOTE: PLEASE PROVIDE A DETAIL FOR |
| | CURBING REQUIRED AROUND BUS-DUCT ON |
| | FLOOR PENETRATIONS WHERE A VERTICAL |
| | RISER PENETRATES TWO OR MORE DRY FLOORS, |
| | A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL |
| | BE INSTALLED AROUND ALL FLOOR OPENINGS |
| | FOR RISER BUSWAYS TO PREVENT LIQUIDS |
| | FROM ENTERING THE OPENING. PER 368.6 |
| | |
| | 3)NOTE: PLEASE PROVIDE BATTERY BACK UP |
| | LIGHT FIXTURES IN ALL ELECTRICAL ROOMS, |
| | ELEVATOR EQUIPMENT ROOMS AND FIRE PUMP |
| | RM. |
| | THIS IS REQUIRED PER FIRE MARSHALS |
| | OFFICE AND AHJ FOR LIGHTING WHICH BE |
| | REQUIRED UNDER NFPA-101 7.8,7.9. |
| | |
| | 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR |
| | STAIR/CORRIDOR AREAS FOR EGRESS TO THE |
| | PUBLIC RIGHT OF WAY. PLEASE SEE 2003 |
| | 101, 7.8 AND 7.9, WHICH REQUIRES 10FT |
| | CANDLES FOR STAIR AREAS AND 1FT FOR |
| | CORRIDOR. |
| | 7.8.1.3,7.9.2.1 |
| | |
| | 5)NOTE: PLEASE SEE MISSING CIRCUITING |
| | FOR FRIG IN UNIT "A". |
| | |
| | 6)NOTE: PLEASE PROVIDE DETAIL FOR ROOF |
| | TOP LT POLES AND FIXTURES. PLEASE |
| | PROVIDE WIND LOAD CALCULATIONS FOR |
| | REVIEW. THIS IS REQUIRED AT THIS TIME |
| | FOR FIXTURES AND POLES. |
| | CALCULATIONS WILL BE REVIEWED BY THE |
| | BLDG REVIEWER FOR CODE COMPLIANCE OF FBC |
| | 140 MPH WIND LOADS. |
| | |
| | 7)NOTE: PLEASE SUBMIT A COMPLETED |
| | LIGHTING FIXTURE SCHEDULE TO CORRELATE |
| | WITH FIXTURES AS SHOWN ON PLANS. |
| | PLEASE ALSO SEE COMMON AREAS WHERE |
| | FIXTURES DO NOT INDICATE WHAT TYPE ETC. |
| | RECREATION AREA, ROOF TOP ETC. |
| | |
| | 8)NOTE: PLEASE MAKE REFERENCE/ NOTES |
| | PERTAINING TO ALL THE ELECTRICAL |
| | REQUIREMENTS FOR ELECTRICAL DEVICES |
| | UNDER FAIR HOUSING ACT REGULATIONS, CFR |
| | 24 100.205. |
| | |
| | 9)NOTE: PLEASE SEE 2002 NFPA-72 11.8.3.5 |
| | FOR SMOKE DETECTOR PLACEMENT. PLEASE |
| | KNOW ALL SD'S ARE REQUIRED TO BE WITH-IN |
| | 12" OF A CEILINGIN FALT CEILING |
| | INSTALLATIONS. PLEASE SEE SD'S WHICH |
| | SEEM TO BE LOCATED AT AREAS OF SOFFIT |
| | ETC SHALL BE MOVED TO AREAS WHERE |
| | CEILINGS WITH HIGHEST POINT. |
| | IF SD'S ARE WALL MOUNTED, THEY ARE STILL |
| | REQUIRED TO BE WITH IN 12" OF CEILING |
| | BUT NO CLOSER THAN 4". |
| | PLEASE ALSO PLACE NOTE ON PLANS FOR SD |
| | PALCEMENT PER ABOVE WITH RESPECT TO SD'S |
| | BEING LOCATE NO CLOSER THAN 3' OF BATH |
| | AND KIRTCHEN DOORS AND NO CLOSER THAN |
| | 20' OF COOKING APPLIANCES, (UNLESS |
| | MEETING EXCEPTIONS AS SET FORTH) AS |
| | LISTED IN NFPA-72 |
| | |
| | 10)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| | ALONG KITCHEN COUNTERSPACES AND |
| | PENINSULARS. |
| | 210.52C1,210.52C3 |
| | PLEASE SEE REDLINED PLANS FOR LOCATIONS. |
| | UNIT, B |
| | |
| | 11)NOTE: PLEASE SEE SOME RECEPTS MISSING |
| | PER 210.52, 2' OF WALL SPACE. |
| | ONCE AGAIN, SEE REDLINED PLANS FOR AREAS |
| | AS NOTED. UNIT , E, A |
| | |
| | 12)NOTE: PLEASE LIST ALL ARC FAULT |
| | PROTECTED CIRCUITS AS REQUIRED UNDER THE |
| | 2002 NEC 210.12. THIS REQUIRES ALL |
| | "OUTLETS" TO BE AF PROTECTED. THIS |
| | INCLUDES SD'S, LTS, RECEPTS , FANS ETC. |
| | |
| | 13)NOTE: PLEASE SEE UNIT "A" WHICH SHOWS |
| | INDIVIDUALS WASHER AND DRYER, HOWEVER |
| | PANEL SCHEDULE SHOWS THIS AS A STACKABLE |
| | UNIT?? |
| | PLEASE SEE "L1A WHICH SHOWS CIRCUIT #24 |
| | AS A SPARE, YET ON PLANS THIS IS SHOWN |
| | FOR ABOVE. |
| | PLEASE CORRELATE. |
| | |
| | 14)NOTE: PLEASE PROVIDE "DINING RM/AREA" |
| | |
| | DESIGNATIONS ON UNITS "A" AND "E". |
| | 210.52B. |
| | |
| | 15)NOTE: PLEASE PROVIDE ROOM/ AREA |
| | DESIGNATIONS ON COMMON AREAS PLANS. |
| | PLEASE SEE ROOMS ETC NOT LABLED. |
| | PLEASE SEE ELECTRICAL PLANS DO NOT |
| | INDICATE "POOL EQUIPMENT " ROOM ETC. |
| | |
| | 16)NOTE: PLEASE SEE 424.3B WHICH |
| | REQUIRES ALL OVERCURRENT PROTECTION FOR |
| | AHU'S HEAT TO BE A MIN OF 125%. |
| | PLEASE SEE THESE AS REDLINED ON PLANS. |
| | PLEASE ALSO REVISE MIN AWG PER 310.16 |
| | ONCE OCP HAS BEEN ADJUSTED. |
| | PLEASE KNOW, MOST OCP IS 150% MAX, |
| | HOWEVER WHEN A AMPERAGE DOES NOT |
| | CORRESPONED TO A COMMON OCP DEVICE AS |
| | LISTED IN 240.6, GOING UP TO THE NEXT |
| | HIGHER OCP IS PERMITTED. |
| | |
| | 17)NOTE: PLEASE SEE MANY OF THE UNITS AS |
| | LISTED ON HOUSE PANELS ALSO NEED TO BE |
| | ADJUSTED. |
| | PLEASE SEE L2B |
| | AHU#10, SHOWS 11KW ON A 2P-30A WITH #10 |
| | AWG. |
| | AHU #11 LISTED TWICE, SHOWS 11KW ON |
| | 2P-45A WITH #8. |
| | AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A |
| | OCP THIS ONE IS OK. |
| | PLEASE SEE AHU#10 IS LISTED TWICE ALSO. |
| | PLEASE SEE AHU #6 ON LRB. |
| | PLEASE SEE AHU #7 ON LRB. |
| | BOTH WITH THE SAME COMMENTS AS LISTED |
| | ABOVE. |
| | PLEASE ADJUST.424.3B,310.16 |
| | |
| | 18)NOTE: PLEASE SEE MIN OCPFOR WATER |
| | HEATER UNITS, SHALL BE A MIN OF 125% AND |
| | A MAX OF 150%. |
| | PLEASE SEE 6KW SHOWN ON A 2P35. |
| | 422.13,422.11E3 |
| | |
| | 19)NOTE:PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. PLEASE SEE THIS IS FOR LOADS |
| | DEDICATED TO HOUSE PANELS, POOL PUMPS, |
| | ANY POOL HEAT PUMPS, LIGHTING , LARGEST |
| | MOTOR STEC. |
| | 215.3,230.42 ETC. |
| | |
| | 20)NOTE: PLEASE BE SURE MAINS 1A,2A,1B, |
| | 2B, INDICATE THAT THE MCB CONTAINS A |
| | MANUAL MEANS OF DISCONNECT LOCATED ON |
| | THE OOUTSIDE OF THE EQUIPMENT AND RATED |
| | FOR THE LOAD SERVED. 230.76 AND 230.79 |
| | PLEASE SEE PLANS ONLY INDUCATE THESE AS |
| | BEING SHUNT TRIP TYPE? |
| | PLEASE ALSO MAKE NOTES FOR MAINS DPA AND |
| | DPB. |
| | |
| | 21)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE |
| | PUMP CONTROLLER. |
| | PLEASE BE SURE NOTES FOR LOCKED ROTOR |
| | AND MANUAL MEANS OF DISCONNECT IS |
| | LOCATED ON PLANS. |
| | PLEASE SEE 695.4B1, |
| | NFPA-20 10.4.2.1.1,10.4.2.2 ETC. |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | AT THIS TIME EVEN IF FIRE PUMP/ |
| | CONTROLLER IS PERMITTED UNDER FIRE |
| | SPRINKLER PERMIT. |
| | |
| | 22)NOTE: PLEASE INDICATE THE EQUIPMENT |
| | GROUNDING CONDUCTORS ON RISER FEEDERS TO |
| | "TAP-BOXES". |
| | 250.110,250.122 |
| | |
| | 23)NOTE: PLEASE SEE FEEDERS FROM MAINS |
| | 1A,2A,1B,AND 2B TO "TAP BOXES |
| | COULD NOT BE LOCATED?? |
| | PLEASE SEE, 215.5,310.16 |
| | |
| | 24)NOTE: PLEASE CORRELATE BUS RISER |
| | DETAILS AND NOTES. PLEASE SEE REDLINED |
| | PLANS, AS THERE ARE 2- "BUSWAY #2 SHOWN, |
| | AND NOTES FOR FEED TO MAIN 2B IS LISTED |
| | TWICE AND ONE IS CROSSED THROUGH?? |
| | PLEASE SEE REDLINED PLANS AND CORRELATE. |
| | 215.5 |
| | |
| | 25)NOTE: PLEASE SEE FEEDERS FROM "DPA" |
| | TO PANEL "L4A" ARE SHOWN AS 3/0'S, |
| | HOWEVER OCP ON DPA IS 400A'S. PLEASE |
| | CORRELATE AND ADJUST. 240.4,310.16 |
| | |
| | 26)NOTE: PLEASE SPECIFY OF PANEL "L4A" |
| | HAS "FEED-THRU " LUGS OR DOES THIS PANEL |
| | CONTAIN OCP FEEDING THRU TO PANEL |
| | "L4AA".? |
| | 215.5 |
| | |
| | 27)NOTE: PLEASE SEE ELEVATOR CIRCUITS AS |
| | LISTED ON DPA #5 AND #6 SHOWS 4-POLES? |
| | FOR A 3-POLE BRKR? |
| | PLEASE ALSO SEE DPB #5 AND #6 AS THIS |
| | SHOWS THE SAME THING. |
| | 215.5 |
| | |
| | 28)NOTE: PLEASE SEE "L1BA" WHICH IS |
| | SHOWN AS A 100A PANEL YET IS BEING FED |
| | WITH A 225A BRKR FROM DPB. |
| | |
| | 29)NOTE: PLEASE SEE PANEL "LPB" WHICH IS |
| | SHOWN AS 200A PANEL, HOWEVER PANEL IS |
| | BEING FED WITH A 225A BRKR FROM "DPB". |
| | PLEASE CORRLEATE. |
| | |
| | 30)NOTE: PLEASE SEE 620.23,620.24 WHICH |
| | REQUIRES DEDICATED CIRCUITS FOR ELEVATOR |
| | PIT LTS AND RECEPTS. THIS CIRCUIT MAY |
| | NOT FEED ANY OTHER LTS AND RECEPTS. |
| | THESE SHALL ALSO BE DEDICATE TO EACH |
| | ELEVATOR/PIT. |
| | PLEASE SEE CIRCUITS FOR ELEVATOR |
| | EQUIPMENT ROOMS SHALL ALSO BE DEDICATED |
| | AND MAY NOT FEED ANY OTHER ROOMS OR |
| | ELECTRICAL LIGHTING OR RECEPTS. |
| | PLEASE ALSO SEE PREVIOUS NOTE WHICH IS |
| | REQUIRING A BATTERY BACK-UP FIXTURE IN |
| | THESE ROOMS. |
| | PLEASE ALSO SEE 700.16D |
| | |
| | 31)NOTE: PLEASE PROVIDE A NOTE ON SHEETS |
| | FOR ELECTRICAL/ ELEVATOR ROOMSWHICH |
| | SHOULD STATE ALL REQUIRED CLEARENCES PER |
| | 110.26 SHALL BE MET FOR ALL ELECTRICAL |
| | EQUIPMENT. (OR WORDS TO THAT AFFECT). |
| | 110.26 |
| | THIS HAS BEEN AN ISSUE IN THIS |
| | JURISDICTION FOR MAINS/METER CENTERS FOR |
| | HEIGHT AND WIDTH OF EQUIPMENT. |
| | |
| | 32)NOTE: PLEASE PLACE NOTE ON "ROOF-TOP" |
| | PLANS WHICH WILL STATE > |
| | "ANY LIGHTNING PROTECTION SYSTEMS WILL |
| | BE REQUIRED TO BE SUBMITTED UNDER A |
| | SEPARATE PERMIT AND PLANS." |
| | "ALL SYSTEMS SHALL MEET NFPA-780." |
| | |
| | 33)NOTE: PLEASE SEE RISER DIAGRAM SEEMS |
| | TO SHOW ELEVATOR EQUIPMENT/ DISCONNECTS, |
| | ETC ON 2ND FLR, HOWEVER PLANS FOR ROOMS |
| | ON E7.1, APPEAR TO SHOW THIS EQUIPMENT |
| | LOCATED ON 1ST FLR?? |
| | |
| | ** PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| | HAVE BEENREDLINED ON PLANS FOR AREAS |
| | OF COMMENTS. |
| | |
| | **PLEASE SEE ALL COMMENTS FROM ALL OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE SEE FIRE REVIEW COMMENTS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONE SET OF ALL OL/VOIDED |
| | SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DONOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |