| 2006-01-06 00:00:00 | PERMIT NUMBER: 05090156 |
| | ADDRESS: 3701 N MILITARY TRAIL |
| | CONTRACTOR: TOWN AND COUNTRY HOMES |
| | FOUR STORY R2 WITH PARKING GARAGE |
| | TYPE II SPRINKLERED |
| | CODE EDITION: 2001 FBC |
| | --------------------------------------- |
| | DENIED |
| | |
| | 1) STRUCTURE IS A THRESHOLD BUILDING PER |
| | FLORIDA STATUES FS 553.71. |
| | FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 2)WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 3)W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CON- |
| | TAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH |
| | THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4) CONDOMINIUM V APARTMENTS.IF THE |
| | DWELLING UNITS ARE TO BE SOLD AS |
| | CONDOMINIUMS, A 'DECLARATION OF |
| | CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| | STATE FOR APPROVAL, AND THEN RECORDED |
| | WITH THE CLERK OF THE COUNTY COURT.A |
| | RECORDED COPY SHALL BE SUBMITTED TO THE |
| | CITY FOR RECORDS, ADDRESSING PURPOSES, |
| | AND TO PALM BEACH COUNTY PROPERTY |
| | APPRAISER'S OFFICE PRIOR TO C.O. |
| | |
| | 5 ) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. REQUIRES 3,00O PSF. |
| | |
| | 6) THREE (3) COMPLETE SETS OF PLANS, |
| | SPECIFICATIONS AND DOCUMENTS ARE |
| | REQUIRED FOR THRESHOLD BUILDINGS. |
| | |
| | 7) SUBMIT (3) SETS OF ENGINEERED LAYOUTS |
| | AND TRUSS DRAWINGS FOR THE METAL TRUSSES |
| | THAT HAVE BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. |
| | |
| | 8) SPECIFY THE ATTACHMENT SPACING AND |
| | FASTENERS FOR THE FIRETREATED PLYWOOD |
| | SHEATHING ON THE METAL TRUSSES. |
| | |
| | 9) THE ALPINE TSUC3 TRUSS CONNECTORS |
| | SPECIFIED FOR THE METAL TRUSSES ON S10 |
| | AND S11 DO NOT HAVE STATE PRODUCT |
| | APPROVAL. SPECIFY TRUSS CONNECTORS WITH |
| | CURRENT STATE OF FLORIDA PRODUCT |
| | APPROVALS PER F.A.C. RULE 9B-72. SUBMIT |
| | PRODUCT APPROVALS WITH STATE COVERSHEET |
| | FOR THE TRUSS CONNECTORS. |
| | |
| | 10) SPECIFY THE ATTACHMENT METHOD THAT |
| | WILL BE USED TO ATTACH THE CEMENT ROOF |
| | TILES AND RESIST THE REQUIRED UPLIFT |
| | MOMENT. |
| | |
| | 11) REVISE THE ROOF RIDGE DETAIL #11 ON |
| | A8.3.1. WHICH DOES NOT MEET THE REQUIRED |
| | UPLIFT MOMENT. |
| | |
| | 12) SUBMIT (3) SETS OF ENGINEERED SHOP |
| | DRAWINGS AND LAYOUTS FOR THE PRECAST |
| | SYSTEM FOR THE PARKING GARAGE. |
| | |
| | 13) THE WALLS SEPARATING THE EXTERIOR |
| | EXIT STAIRS FROM THE INTERIOR OF THE |
| | BUILDING ARE REQUIRED TO HAVE A FIRE |
| | RESISTANCE RATING OF NOT LESS THAN ONE |
| | HOUR PER FBC 1006.2.4. |
| | |
| | 14) ELEVATORS #2 AND #4 ARE NOT LABELED |
| | ON SHEETS A 2.0.2 AND A 2.0.4. |
| | |
| | 15) REFUSE CHUTES ARE REQUIRED HAVE A |
| | TWO (2) HOUR FIRE RESISTANCE RATING WITH |
| | ONE AND A HALF HOUR FIRE RATED OPENING |
| | PROTECTIVES PER FBC TABLE 705.1.2. |
| | DETAIL 5 ON A 4.0.10 SPECIFIES ONLY A |
| | ONE HOUR SHAFT WALL AND DOES NOT SPECIFY |
| | THAT THE DOOR HAS TO BE SELF-CLOSING AND |
| | 1-1/2 HOUR FIRE RATED. SEE FBC 705.2.4.2 |
| | |
| | |
| | 16) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | LISTING FOR THE SELF-CLOSING FIRE RATED |
| | DOORS TO THE REFUSE CHUTE SHAFT AND THE |
| | OPENING PROTECTIVE BETWEEN THE SHAFT AND |
| | THE TERMINATION ROOM. |
| | |
| | 17) IN REGUARD TO FIRE RESISTANCE OF |
| | RESIDENTIAL CORRIDOR WALLS ON SHEET |
| | A1.3.1, FBC TABLE 704.2.4 ALLOWS 1/2 |
| | HOUR RATED WALLS WHEN THE BUILDING IS |
| | SPRINKLERED. FBC TABLE 1004 ALLOWS THE |
| | TRAVEL DISTANCE TO BE INCREASED TO 325 |
| | FT. FOR SPRINKLERED BUILDINGS. HOWEVER, |
| | FBC 903.2 STATES THAT SPRINKLERS |
| | INSTALLED IN LIEU OF OR AS AN ALTERNATE |
| | TO OTHER REQUIREMENTS OF THE CODE SHALL |
| | BE CONSIDERED REQUIRED SYSTEMS AND SHALL |
| | COMPLY WITH NFPA. THEREFORE, THE ENTIRE |
| | BUILDING SHALL COMPLY WITH NFPA 13 AND |
| | THE EXCEPTION TO FBC 903.7.6 WHICH |
| | ALLOWS AN NFPA 13R IN R2 OCCUPANCIES CAN |
| | NOT BE USED. SPECIFY THAT SPRINKLER |
| | SYSTEM IS NFPA 13. |
| | |
| | 18) SHEET A1.3.1 ALSO INDICATES THAT |
| | OPENING PROTECTIVES ARE NOT REQUIRED AT |
| | THE RESIDENTIAL CORRIDOR WALLS BASED ON |
| | FBC 1014.1.1, 1006.2.2 AND 1006.2.4. FBC |
| | 1014.1.1 REQUIES AT LEAST 50 PERCENT OF |
| | THE BALCONY, GALLERY OR SIMILAR SPACE TO |
| | BE OPEN ON THE LONG SIDE. THIS DOES NOT |
| | APPEAR TO BE APPLICABLE TO THESE PLANS. |
| | THEREFORE, WINDOW AND DOOR OPENING |
| | PROTECTIVES WILL BE REQUIRED AT THE EXIT |
| | ACCESS CORRIDORS. THIS ALSO WILL APPLY |
| | TO STORE FRONTS FOR THE REC. AREA AT THE |
| | COVERED EXPANSION. |
| | |
| | 19) PROVIDE A LIFE SAFETY PLAN FOR THE |
| | POOL AND DECK AREA. SPECIFY OCCUPANT |
| | LOADS AND EXITS. |
| | |
| | 20) NO DIMENSIONS ARE GIVEN ON THE REC. |
| | AREA FLOOR PLAN. |
| | |
| | 21) THE OCCUPANT LOAD OF THE CARD ROOM |
| | AND FITNESS CENTER EXCEEDS 50 PERSONS, |
| | THEREFORE, THEY ARE CONSIDERED SMALL |
| | ASSEMBLY OCCUPANCIES REQUIRING TWO HOUR |
| | TENANT SEPARATIONS. SEE FBC 304.1.1, |
| | 704.1.1 |
| | |
| | 22) THE DOUBLE DOORS (#6) FROM THE |
| | MULIPURPOSE ROOM TO THE ONE HOUR FIRE |
| | RATED ACCESS CORRIDOR ARE REQUIRED TO |
| | HAVE A 20 MINUTE FIRE RATING AND BE SELF |
| | CLOSING. SEE FBC 705.1.3.2.3 AND |
| | 705.1.3.2.2 |
| | |
| | 23) THERE IS AN EXIT LIGHT THAT IS |
| | LOCATED IN THE LOCKER ROOM AT A LOCATION |
| | WHERE THERE IS NO EXIT. SEE SHEETS |
| | E1.2.2 AND E2.1.1 |
| | |
| | 24) DOOR #3 ON A4.0.8 IS SPECIFIED AS A |
| | DOUBLE 3'X 8' DOOR ON THE SCHEDULE BUT |
| | IS SHOWN AS A SINGLE DOOR ON THE PLANS. |
| | |
| | 25) ALL FIRE RATED DOORS ARE REQUIRED TO |
| | HAVE APPROVED CLOSERS OR BE SELF |
| | CLOSING. SPECIFY CLOSERS FOR ALL RATED |
| | DOORS PER FBC 705.1.3.2.3. |
| | |
| | 26) SPECIFY THE AMOUNT AND TYPE OF |
| | CHEMICALS THAT WILL BE STORED IN THE |
| | POOL EQUIPMENT ROOM. SPECIFY OCCUPANCY |
| | SEPARATION FOR STORAGE OF HAZARDOUS |
| | MATERIALS. SEE FBC 308 AND 704. |
| | |
| | 27) NO TENANT SEPARATION IS SPECIFIED |
| | BETWEEN THAT POOL STORAGE ROOM AND THE |
| | MAIN ELECTRICAL ROOM ON SHEET A4.0.9. |
| | SPECIFY THE AMOUNT AND TYPE OF POOL |
| | CHEMICALS THAT WILL BE STORED. |
| | |
| | 28) THE SECTION THROUGH THE TRASH ROOM |
| | IS MISSING THE ID TAG. |
| | |
| | 29) FBC 707.1 DOES NOT ALLOW |
| | COMBUSTIBLES IN CONCEALED SPACES OF |
| | PARTITIONS OF TYPE II CONSTRUCTION. |
| | SPECIFY THAT BACKING MUST BE |
| | NON-COMBUSTIBLE OR FIRE RETARDANT |
| | TREATED WOOD. |
| | |
| | 30) PLEASE REVISE NOTES ON A8.2.2 WHICH |
| | REFER TO THE 2001 SOUTH FLORIDA BUILDING |
| | CODE. |
| | |
| | 31) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | LISTINGS FOR THE FIRE RATED WINDOWS AND |
| | DOORS (OPENING PROTECTIVES). |
| | |
| | 32) SUBMIT THE MANUFACTURER,S |
| | SPECIFICATIONS FOR THE CLOSERS REQUIRED |
| | ON THE FIRE RATED DOORS. |
| | |
| | 33) DETAIL 5 ON A8.3.2 APPEARS TO SHOW A |
| | PRIMARY SCUPPER PIPED THROUGH A MANSARD |
| | ROOF. SPECIFY WHERE THIS IS LOCATED. A |
| | PRIMARY SCUPPER WILL BE REQUIRED TO |
| | EMPTY INTO A DOWNSPOUT AND BE DISCHARGED |
| | A MINIMUM OF 12" AWAY FROM THE |
| | FOUNDATION. |
| | |
| | 34) WINDOWS LABELED H AND J WHICH ARE |
| | LOCATED IN THE MULTIPURPOSE ROOM ARE NOT |
| | LISTED IN THE WINDOW SCHEDULE ON SHEET |
| | A4.0.8. |
| | |
| | 35) THE INTERNAL PRESSURE COEFFICENT ON |
| | SHEET S7 IS POSITIVE AND NEGATIVE + OR |
| | -0.18. |
| | |
| | 36) MANY OF THE COLUMNS ARE MISSING THE |
| | ID TAGS ON THE STRUCTURAL DRAWINGS. |
| | |
| | 37) SOME OF THE COLUMNS ON S2.3 APPEAR |
| | TO BE MISSING STUD RAIL ID TAGS. |
| | |
| | 38) CLEARLY INDICATE THE LOCATIONS OF |
| | THE BAHAMA SHUTTERS ON THE PLANS. ARE |
| | THESE FOR DECORATIVE PURPOSES OR ARE |
| | THEY INTENDED TO PROVIDE PROTECTION FROM |
| | WIND BOURNE DEBRIS. IF THE LATTER |
| | COMPLIANCE WITH THE CITY OF WEST PALM |
| | BEACH'S STORM SHUTTER POLICY WILL BE |
| | REQUIRED. |
| | |
| | 39) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. IN |
| | ADDITION TO THE FL# COVERSHEET THE |
| | EVALUATION REPORT AND INSTALLATION |
| | INSTRUCTIONS ARE REQUIRED. |
| | |
| | 40) THE NOA (EVALUATION REPORT) |
| | SUBMITTED FOR THE BAHAMA SHUTTERS IS |
| | EXPIRED. SUBMIT CURRENT FL COVERSHEET |
| | AND EVALUATION REPORT FOR THE SHUTTERS. |
| | SUBMIT AN INSTALLATION SCHEDULE WITH |
| | OPENING SIZES, SHUTTER WIDTHS AND SPANS, |
| | AND A KEY PLAN. |
| | |
| | 41) SUBMIT PRODUCT APPROVALS FOR DOORS |
| | #S 1,7 AND 8 WITH THE SMALL LOUVERS |
| | LISTED IN THE COMMON AREA DOOR SCHEDULE |
| | ON A10.0.1. THE PRODUCT APPROVALS |
| | SUBMITTED ARE FOR FULL LOUVER DOORS. |
| | |
| | 42) SUBMIT PRODUCT APPROVALS AND |
| | MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | FIRE RATED DOORS AND WINDOWS. |
| | |
| | 43) SUBMIT THE SBCCI REPORT # 2203 THAT |
| | IS LISTED ON THE STATE WEBSITE AS THE |
| | EVALUATION REPORT FOR THE HANSON ROOF |
| | TILES. |
| | |
| | 44) THE INGERSOLL-RAND DOOR PRODUCT |
| | APPROVALS HAVE THE WRONG NOAS |
| | (EVALUATION REPORTS) ATTACHED TO THE |
| | FL# COVERSHEETS. |
| | |
| | 45) SUBMIT THE FL COVERSHEET FOR THE |
| | L-3000 WINDOW WALL SYSTEM. |
| | |
| | 46) THE PGT FL COVERSHEET FOR THE FRENCH |
| | DOOR IS ATTACHED TO AN ARCH ALUMNIUM |
| | NOA. |
| | |
| | 47) THE PGT COVERSHEET AND NOA FOR |
| | FL#251 THE SLIDING GLASS DOORS DOES NOT |
| | INCLUDE TRIPLE SLIDING GLASS DOOR |
| | CONFIGURATION. SUBMIT PRODUCT APPROVALS |
| | FOR THE TRIPLE SLIDING GLASS DOORS. |
| | |
| | 48) THE THERMA-TRUE/ BENCH MARK DOORS |
| | WILL NEED TO HAVE A FIRE RATING IF USED |
| | AT THE EXIT ACCESS CORRIDORS. |
| | |
| | 49) SUBMIT PRODUCT APPROVALS FOR THE |
| | ROOFING SYSTEM THAT WILL BE USED ON THE |
| | FLAT ROOF AREAS OF THE BUILDING. |
| | |
| | 50) SUBMIT A SITE PLAN SHOWING |
| | ACCESSIBLE ROUTES TO ALL BUILDINGS, |
| | AMENITIES, PARKING AND TO THE PUBLIC WAY |
| | AS REQUIRED BY FBC 11-4.1.2, THE FAIR |
| | HOUSING ACCESSIBILITY GUIDELINES AND |
| | ANSI 4.3. SHOW CURB RAMPS, SIDE WALK |
| | WIDTHS, SIGNAGE, DETECTABLE WARNINGS, |
| | CROSSWALKS,ETC. |
| | |
| | 51) THE MAILBOXES ARE REQUIRED TO BE |
| | ACCESSIBLE. |
| | |
| | 52) SPECIFY THE LOCATION OF THE ON |
| | STREET ACCESSIBLE PARKING SPACES |
| | SPECIFIED IN THE SCHEDULE ON A0.0.5. |
| | |
| | 53) SPECIFY THE NUMBER OF PARKING SPACES |
| | IN THE PARKING GARAGE AND THE NUMBER OF |
| | ACCESSIBLE SPACES IN THE SCHEDULE ON |
| | A0.0.5. IN PARKING STRUCTURES ONE IN |
| | EVERY EIGHT ACCESSIBLE SPACES, BUT NOT |
| | LESS THAN ONE, SHALL BE VAN ACCESSIBLE. |
| | SEE FBC 11-4.1.2, 11-4.6.4 AND 11-4.6.5. |
| | |
| | NOTE: GARAGE DOES NOT APPEAR TO PROVIDE |
| | THE REQUIRED VERTICAL CLEARANCE FOR THE |
| | VAN ACCESSIBLE PARKING. ALSO CONSIDER |
| | CLEARANCES TO SPRINKLER PIPES, DRAIN |
| | PIPES, ETC. |
| | |
| | 54) THE UNIT E AND ER DWELLING UNITS ON |
| | A407 AND A407A HAVE ONE BATHROOM |
| | SPECIFIED AS "TYPE A" AND THE OTHER AS |
| | "TYPE B". THIS IS INCORRECT. IF |
| | "SPECIFICATION A" IS SELECTED AS THE |
| | BASIS FOR DESIGNING A BATHROOM IN |
| | DWELLING UNITS WITH MORE THAN ONE |
| | BATHROOM, THEN ALL OF THE BATHROOMS IN |
| | THE DWELLING UNIT MUST COMPLY WITH THE |
| | "A SPECIFICATIONS". IF "SPECIFICATION B" |
| | IS SELECTED ONLY ONE BATHROOM IN THE |
| | DWELLING UNIT MUST MEET THOSE |
| | REQUIREMENTS; ALL OTHER BATHROOMS IN THE |
| | DWELLING UNIT MUST BE ON AN ACCESSIBLE |
| | ROUTE, HAVE DOORS WITH A NOMINAL 32-INCH |
| | CLEAR OPENING, HAVE SWITCHES, OUTLETS, |
| | AND CONTROLS IN ACCESSIBLE LOCATIONS, |
| | AND HAVE REINFORCED WALLS AROUND |
| | TOILETS, TUBS, AND SHOWER STALLS. SEE |
| | CHAPTER 7 OF THE FAIR HOUSING DESIGN |
| | MANUAL. |
| | |
| | 55) A SEPARATE PERMIT WILL BE REQUIRED |
| | FOR THE POOL, GAZEBOS AND TOT LOT. |
| | NOTE: THESE ITEMS WILL BE REVIEWED FOR |
| | ACCESSIBILITY. PLAY AREA WILL BE |
| | REQUIRED TO COMPLY WITH ADA |
| | ACCESSIBILITY GUIDELINES FOR PLAY AREAS. |
| | |
| | 56)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 57) LIFE SAFETY NOTE #4 ON A1.3.1 STATES |
| | THAT THE OPEN, COVERED EGRESS CORRIDORS |
| | ARE SPRINKLERED, HOWEVER, THE FIRE |
| | SPRINKLER PLANS DO NOT INDICATE THIS. |
| | |
| | 58) ON A2.1.13 THERE IS A NOTE THAT |
| | REFERS TO SHEET A2.1.14 FOR PARKING |
| | SPACES IN THIS AREA. THERE WAS NO SHEET |
| | A2.1.14 IN THIS PLAN SET. |
| | |
| | 59) THE ROOF ACCESS DOORS FROM THE |
| | STAIRS SHALL HAVE KEYED LOCKSETS AND |
| | SIGNAGE TO PREVENT PUBLIC ACCESS. |
| | |
| | 60) THE CALCULATED VALUE OF THE |
| | STRUCTURE BASED ON AREA BREAKDOWN ON |
| | PLANS IS $23,667,187.00. FEES HAVE BEEN |
| | ADJUSTED. |
| | |
| | 61) ADDITIONAL COMMENTS MAY RESULT FROM |
| | RESPONSES TO THESE ISSUES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |