| 2005-10-04 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- KEY PLAN SUBMITTED DOESN'T INDICATE |
| | WHICH OPENING IS GOING TO BE USED FOR |
| | EMERGENCY EGRESS AS REQUIRED BY SEC. |
| | 1005.4.5 FBC 2001. PLEASE INDICATE |
| | EMERGENCY EGRESS OPENING. OPENING CAN'T |
| | BE IN GARAGE. SEE SEC. 1005.4.5 FBC 2001 |
| | FOR ADDITIONAL RESTRICTIONS. |
| | |
| | 2- NOTE: THERE ARE 3 DIFFERENT TYPES OF |
| | TAPCONS AND THEY HAVE DIFFERENT VALUES. |
| | CLEARLY INDICATE ON DRAWING 5 OF 6 OF |
| | ALUM. STORM PANELS SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED ACCORDING TO THE |
| | DESIGN PRESSURES, EDGE DISTANCE, PANEL |
| | SPAN, CONNECTION TYPE AND STRUCTURE TO |
| | BE ATTACHED TO IN ORDER TO VERIFY |
| | COMPLIANCE. UNABLE TO DETERMINE |
| | COMPLIANCE IF SPECIFIC TAPCON IS NOT |
| | SPECIFIED. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 3- DRAWING 5 OF 5 OF ACCORDION SHUTTERS |
| | DRAWINGS WAS CIRCLED SHOWING TAPCON |
| | ANCHOR FOR UP TO 6"-0" PANEL SPAN AND |
| | CONNECTION TYPE C2. ACCORDING TO THE |
| | INSTALLATION SCHEDULE THE ACCORDION |
| | SHUTTER IS 88" LONG. REVISE DRAWING 5 OF |
| | 5 AND INSTALLATION SCHEDULE AS REQUIRED. |
| | |
| | |
| | 4- VALUATION DECLARED ON THE PERMIT |
| | APLICATION IS TOO LOW. UPGRADE VALUE A S |
| | REQUIRED OR IT WILL BE ESTIMATED USING |
| | THE MARSHALL & SWIFT VALUATION SERVICE. |
| | |
| | 5- WILL NEED RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |