2005-10-04 00:00:00BUILDING REVIEW CHECKLIST:
 1- KEY PLAN SUBMITTED DOESN'T INDICATE
 WHICH OPENING IS GOING TO BE USED FOR
 EMERGENCY EGRESS AS REQUIRED BY SEC.
 1005.4.5 FBC 2001. PLEASE INDICATE
 EMERGENCY EGRESS OPENING. OPENING CAN'T
 BE IN GARAGE. SEE SEC. 1005.4.5 FBC 2001
 FOR ADDITIONAL RESTRICTIONS.
  
 2- NOTE: THERE ARE 3 DIFFERENT TYPES OF
 TAPCONS AND THEY HAVE DIFFERENT VALUES.
 CLEARLY INDICATE ON DRAWING 5 OF 6 OF
 ALUM. STORM PANELS SPECIFIC ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO IN ORDER TO VERIFY
 COMPLIANCE. UNABLE TO DETERMINE
 COMPLIANCE IF SPECIFIC TAPCON IS NOT
 SPECIFIED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 3- DRAWING 5 OF 5 OF ACCORDION SHUTTERS
 DRAWINGS WAS CIRCLED SHOWING TAPCON
 ANCHOR FOR UP TO 6"-0" PANEL SPAN AND
 CONNECTION TYPE C2. ACCORDING TO THE
 INSTALLATION SCHEDULE THE ACCORDION
 SHUTTER IS 88" LONG. REVISE DRAWING 5 OF
 5 AND INSTALLATION SCHEDULE AS REQUIRED.
  
  
 4- VALUATION DECLARED ON THE PERMIT
 APLICATION IS TOO LOW. UPGRADE VALUE A S
 REQUIRED OR IT WILL BE ESTIMATED USING
 THE MARSHALL & SWIFT VALUATION SERVICE.
  
 5- WILL NEED RECORDED NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.