Plan Review Notes
Plan Review Notes For Permit 05090131
Permit Number 05090131
Review Stop P
Sequence Number 4
Notes
Date Text
2008-03-07 09:38:57REVISION DENIED;
 1. RISER DIAGRAM NOT TO CODE, BIDET IS NOT VENTED.
 2. RISER DIAGRAM NOT TO FLOOR PLAN;
 A) 2 W/M'S AND 2 L/T'S SHOWN ON RISER
 DIAGRAM ONLY ONE SHOWN ON PLANS.
 B) LAVATORY FOR BATH #1 MISSING FROM
 RISER DIAGRAM.
 C) TUB SHOWN IN BATHROOM # 1 ON RISER
 DIAGRAM NOT SHOWN ON FLOOR PLAN.
 D) REVISED RISER DIAGRAM REVIEWED DEC. 9
 TH 2006 SHOWS A SEWAGE PUMP ADDED TO RISER DIAGRAM, NOT
 SHOWN ON THIS DIAGRAM
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695