| Notes |
| Date |
Text |
| 2005-09-29 00:00:00 | DENIED; | | | 1.FBC-2001 FUEL GAS SEC303.3 WATER | | | HEATER IS NOT PERMITED IN A BATHROOM. IF | | | A DOOR IS INSTALLED IT MUST HAVE WEATHER | | | STRIPING AROUND GAM AND A THESHOLD MUST | | | BE INSTALLED, ALSO SHOW MEANS OF | | | COMBUSTION AIR FOR WATER HEATER SEE | | | FBC-2001 FUEL GAS SEC. 304.4.2. | | | 2.SUBMIT INSTALLATION INSTRUCTION FOR | | | GAS HOT TUB, MAY NOT BE PROMITED ON WOOD | | | PORCH. | | | 3.SANITARY RISER DIAGRAM IS NOT TO CODE. | | | NOT PROPERLY VENTED. | | | DONOT SHOW A TRAP FOR W/C TRAP IS | | | BUILT INTO THE TOILET. | | | ONE SET OF PLANS ARE MARKED IN RED | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|