| Plan Review Notes For Permit 05090131 |
| Permit Number |
05090131 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-27 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON RESPONSIBLE FOR THE PLANS | | | MUST PRINT THEIR NAME AND SIGN SAME. | | | 104.2.1 FBC | | | | | | 2} THE LOAD CALCULATION DOES NOT INCLUDE | | | THE HOT TUB. | | | | | | 3} THE PANEL SCHEDULE DOES NOT INDICATE | | | COMPLIANCE WITH 210.11(C)(3) FOR THE | | | BATH CIRCUITS. THE PLAN ALSO SHOWS THE | | | CICUITS THEY ARE ON EXTENDING OUTSIDE | | | THE BATHROOM. | | | | | | 4} SHOW COMPLIANCE WITH 225.31 AND | | | 250.32 FOR ALL SEPERATE STRUCTURES. THIS | | | CAN BE DONE ON THE RISER DIAGRAM. | | | | | | 5} PLEASE SEE THE REVIEWED SET OF PLANS. | | | SMOKE DETECTORS ARE REQUIRED OUTSIDE OF | | | THE SLEEPING AREA AS WELL AS INSIDE. | | | SEE 8-1.4.1.6.2 NFPA-72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|