Plan Review Notes
Plan Review Notes For Permit 05090131
Permit Number 05090131
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-27 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON RESPONSIBLE FOR THE PLANS
 MUST PRINT THEIR NAME AND SIGN SAME.
 104.2.1 FBC
  
 2} THE LOAD CALCULATION DOES NOT INCLUDE
 THE HOT TUB.
  
 3} THE PANEL SCHEDULE DOES NOT INDICATE
 COMPLIANCE WITH 210.11(C)(3) FOR THE
 BATH CIRCUITS. THE PLAN ALSO SHOWS THE
 CICUITS THEY ARE ON EXTENDING OUTSIDE
 THE BATHROOM.
  
 4} SHOW COMPLIANCE WITH 225.31 AND
 250.32 FOR ALL SEPERATE STRUCTURES. THIS
 CAN BE DONE ON THE RISER DIAGRAM.
  
 5} PLEASE SEE THE REVIEWED SET OF PLANS.
 SMOKE DETECTORS ARE REQUIRED OUTSIDE OF
 THE SLEEPING AREA AS WELL AS INSIDE.
 SEE 8-1.4.1.6.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved