| Plan Review Notes For Permit 05090114 |
| Permit Number |
05090114 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-11-15 00:00:00 | 1) A NOTORIZE LETTER SIGNED BY THE OWNER | | | AGREEING TO STATEMENT IN THE 2004 FBC | | | SEC.3105.5. WHICH STATES THAT THE AWNING | | | SHALL BE REMOVED OR REPOSITIONED DURING | | | PERIODS OF HIGH WINDS OF 90MPH, 3-SECOND | | | WIND GUST. | | | | | | 2)SHOW HOW AWNING WILL BE DESIGNED TO | | | THE 140MPH BASIC WIND SPEED.FBC. | | | 1606.1.6 AND 1606.1.7 ALSO SEE 2004 FBC. | | | SEC.3105.4 | | | | | | 3) AWNINGS, CANOPIES, MARQUEES AND SIGNS | | | WITH LESS THAN 15 FEET CLEARANCE ABOVE | | | THE SIDEWALK SHALL NOT EXTEND INTO OR | | | OCCUPY MORE THAN TWO-THIRDS THE WIDTH OF | | | THE SIDEWALK MEASURE FROM THE BUILDING. | | | 2004 FBC. 3202.3.1. SHOW THE HEIGHT OF | | | THE AWNING FROM THE LOWEST POINT TO THE | | | SIDE-WALK IMMEDIATELY BELOW. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 | | | [email protected] |
|