| Date |
Text |
| 2005-09-10 00:00:00 | ************UNSST ************* |
| | |
| | 1)NOTE: PLEASE SEE PLANS MENTIONS, |
| | "WAREHOUSE" , HOWEVER 2ND FLR AREA SEEMS |
| | TO BE CHNAGED TO A RESIDENTIAL |
| | DWELLING/APT. |
| | PLEASE SEE FULL KITCHEN/ BATH ETC BEING |
| | PROVIDED. |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT THE PLANS. |
| | EGRESS INTO WAREHOUSE ETC |
| | |
| | 2)NOTE: PLEASE SEE FIRE REVIEWCOMMENTS |
| | FOR MISSING EGRESS LT REQUIRED. PLEASE |
| | SEE NFPA 101 7.8 AND 7.9 . |
| | PLEASE ALSO SEE AREAS WHERE A "J"-BOX IS |
| | BEING SHOWN AND NO LIGHTING IS PROVIDED. |
| | PLEASE SEE BATHS ETC. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUTING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | TO BE SUBMITTED. |
| | 215.5, PLEASE ALSO SEE 700.12E WHICH |
| | REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT (EM/EXT LTS) SHALL BE THE |
| | SAME BRANCH CIRCUIT AS THAT SERVING THE |
| | NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| | |
| | 4)NOTE: PLEASE SUBMIT A RISER DIAGRMA |
| | SHOWING ANY NEW OR EXSITING ELECTRICAL |
| | EQUIPMENT TO BE INSTALLED ETC. IF THIS |
| | BLDG WAS DAMGED TO THE POINT AS STATED |
| | ON PLANS, ALL EXISTING ELECTRICAL PANELS |
| | MAY ALREADY BE REQUIRED TO BE REPLACED |
| | DUE TO CONTAMINATION OF BUS/BRKRS ETC. |
| | 110.11 |
| | |
| | 5)NOTE: PLEASE ALSO SUBMIT ELECTRICAL |
| | LOAD CALCULATIONS FOR NEW ELECTRICAL . |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| | SHOWN AT 125%, 215.3,230.42 ETC. |
| | |
| | 6)NOTE: PLEASE SEE IF ZONING, BLDG ETC |
| | APPROVES DWELLING UNIT ON 2ND FLR, |
| | PLEASE SEE 210.8A6 FOR ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE. |
| | IF USE IS GOING TO BE COMMERCIAL, THEN |
| | PLEASE SEE 210.8B3 FOR KITCHENS IN OTHER |
| | THAN DWELLING UNITS. |
| | |
| | 7)NOTE: PLEASE 600.5 FOR REQUIRED SIGN |
| | CIRCUIT. |
| | |
| | 8)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION REQUIRED ON TITLE BLOCK PER |
| | FAC 61G1-16.004, FS 481.219 |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | |
| | 9)NOTE: PLEASE VERIFY HOW NEW DIPOSAL IN |
| | KITCHEN WILL BE CONTROLLED. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 561-805-6717 |
| | [email protected] |