Plan Review Notes
Plan Review Notes For Permit 05090096
Permit Number 05090096
Review Stop B
Sequence Number 4
Notes
Date Text
2006-08-17 00:00:00 
 1) INDICATE CLEARLY IF THIS FILM WILL BE
 USED ON ALL THE WINDOWS THROUGHOUT THE
 HOUSE. THE SIZE OF THE GLAZING IN THE
 FILM REPORT IS 3/16.HOWEVER PRODUCT
 APPROVAL FOR THE WINDOWS SHOWS THE
 GLAZING SIZE OF 3/32 ANNEALED OR 1/8
 TEMPERED. SEE THE DESCRIPTION OF UNIT ON
 PG2, WHERE THE MENTION OF SLIDING GLASS
 DOOR SASH NO WINDOW. ALSO SEE
 INSTALLATION DETAILS. IS THE
 CONSTRUCTION OF THE STRUCTURE WOOD OR
 CONCRRETE?
  
 2) NO DRAWINGS WERE PROVIDED HOWEVER,
 THE REPORT INDICATES THAT HETI STAMPED
 DRAWINGS IS AN INTEGRAL PART OF THIS
 REPORT. SO WHERE ARE THE DRAWINGS?
  
 3) THIS SEEMS TO BE AN OLD REPORT.
 SUBMIT AN UP-DATED REPORT WITH THE
 ORIGINAL SEAL AND SIGNATURE OF THE P.E.
  
 4) ADDITIONAL INFORMATION IS REQUIRED
 REGARDING THE USE OF THE FILM. WILL THE
 STORM PANELS USED ALONG WITH THE FILM OR
 WILL THE PANELS BE ELIMINATED?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  