| Date |
Text |
| 2006-01-11 00:00:00 | **** UNSAT 2ND REVIEW ****** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STTILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE NEW NOTES DUE TO SOME |
| | CHANGES IN PLANS. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO. |
| | THE PERMIT APPLICATION NOW MENTIONS A |
| | VALUE OF $67,000, HOWEVER THIS VALUE IS |
| | NOT APPROPRIATE FOR SCOPE OF WORK, ALL |
| | LABOR AND MATERIALS. |
| | PLEASE KNOW, EVEN IF EQUIPMENT IS OWNER |
| | SUPPLIED, THE VALUE SHALL BE INLCUDED. |
| | WHEN RESUBMITTED , PLEASE HAVE VALUE |
| | INCREASED AT THAT TIME. IF VALUE IS NOT |
| | ADJUSTED FOR THE FOLLOWING REVIEW, ONE |
| | WILL BE ASSESSED. 104.6.5 |
| | |
| | 2)NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE PANEL DP1 |
| | IS NOW BEING SHOWN AS A MCB, HOWEVER |
| | PLEASE SEE FEEDERS FROM ATS (FIRST MEANS |
| | OF DISCONNECT) TO THIS DP1. AS PER SPECS |
| | FOR ATS SUBMITTED, THE ATS DOES NOT |
| | CONTAIN A MANUAL MEANS OF DISCONNECT |
| | LOCATED ON THE OUTSIDE OF THE EQUIPMENT |
| | RATED FOR THE LOAD SERVED AS REQUIRED |
| | PER 230.76, 230.79. |
| | PLEASE SEE THE SPECS DO INDICATE A |
| | MANUAL SWITCH, HOWEVER NOTES AS BEING |
| | FOR NEMA 1 LOCATION ONLY. PLEASE SEE |
| | THIS ATS IS LOCATED OUTSIDE. |
| | THIS ATS ALSO NOT INDICATE BEING RATED |
| | AS SERVICE ENTRANCE AS REQUIRED. |
| | PLEASE SEE A DISCONNECTING MEANS MAY BE |
| | INSTALLED FROM METER/CT TO THE ATS AND |
| | ANOTHER DISCONNECT FROM GEN TO ATS, |
| | GROUPED AS REQUIRED BY 230.72,225.34 AND |
| | THE MCB WOULD NOT BE REQUIRED IN PANEL |
| | DP1. |
| | THIS IS ONLY ONE POSSIBLE METHOD. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | |
| | 7)NOTE: NOTE # 7 OK. |
| | |
| | 8)NOTE: NOTE #8 OK, HOWEVER PLEASE SEE |
| | NOTES FOR REVIEW OF SPECS. |
| | |
| | 9)NOTE: NOTE # 9 OK. |
| | |
| | NEW NOTE; |
| | |
| | 1)NOTE: PLEASE SEE PLANS WERE ORIGINALLY |
| | SINED , DATED AND SEALED BY AN ENGINEER |
| | OF RECORD AS REQUIRED, HOWEVER NOW PLANS |
| | ARE COMING BACK SIGNED AND SEALED BY AN |
| | ARCH?? |
| | PLEASE SEE SCOPE OF WORK REQUIRES THE |
| | EELCTRICAL PLANS TO BE DONE BY AN |
| | ENGINEER AND ANOTHER DESIGNER MAY NOT |
| | SIGN AND SEAL ANOTHER DESIGNERS WORK. |
| | FS 481, 471. |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |