| 2005-09-30 00:00:00 | ************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE VALUATION SHALL BE |
| | BASED ON ALL LABOR AND MATERIALS EVEN IF |
| | MATERIALS ARE OWNER SUPPLIED. |
| | THIS WOULD ALSO INCLUDE ALL OTHER |
| | PERMANANTLY INSTALLED EQUIPMENT IE: DC |
| | SYSTEM, ETC |
| | PLEASE KNOW A VALUE WILL BE ACCESSED BY |
| | THIS OFFICE IF NOT ADJUSTED BY |
| | CONTRACTOR. |
| | THIS WOULD INCLUDE ALL ELECTRICAL |
| | EQUIPMENT , GENERATOR ETC. |
| | FBC 104.6.5, ADMINISTRATIVE AMENDMENTS. |
| | |
| | 2)NOTE: PLEASE CORRELATE PLANS, ONE |
| | SHEET INDICATES GENERATOR TO BE A MOBILE |
| | UNIT WITH SOME SORT OF TAP BOX? |
| | PLANS AND SUBMITTALS ALSO DO NOT REFLECT |
| | THIS AND SHOWS A PERMANANTLY INSTALLED |
| | GEN ETC.?? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE INSTALLED A DISCONNECT |
| | FOR FEEDERS COMING FROM GENERATOR AT |
| | BLDG. |
| | THIS MEANS OF DISC SHALL BE GROUPED WITH |
| | OTHER MAINS AND RATED FOR THE LOAD |
| | SERVED. |
| | PLEASE SEE 225.31-225.39,110.27 ETC. |
| | A MCB MAY BE INSTALLED IN DP1 WHICH NOW |
| | INDICATES BEING A MLO. |
| | SIGNAGE WILL BE REQUIRED, 230.2E, 702.8 |
| | ETC |
| | |
| | 4)NOTE: PLEASE CLARIFY DOOR/ WINDOW |
| | WHICH IS SHOWN ON PLANS? |
| | IF A MEANS OF EXIT, SEE FIRE REVIEW |
| | COMMENTS FOR ANY EXT LT WHICH MAY BE |
| | REQUIRED. |
| | |
| | 5)NOTE: PLEASE SEE "TAP BOX" AS SHOWN |
| | WILL NOT MEET THE DISCONNECTING MEANS |
| | REQUIRED. |
| | |
| | 6)NOTE: PLEASE SHOW LOCATION OF ALL ASSC |
| | GEN EQUIPMENT. |
| | PLEASE SHOW LOCATION OF GEN STATUS |
| | PANEL. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE INCLUDED COLD WATER PIPE |
| | IN GROUNDING DETAIL FOR SERVICE. |
| | 250.50 |
| | |
| | 8)NOTE: PLEASE SUBMIT TWO COPIES OF ALL |
| | MANUFACTURES SPEC/CUT SHEETS FOR GEN |
| | ETC. |
| | PLEASE SEE ONLY ONE SET WAS SUBMITTED. |
| | PLEASE ALSO INLCUDE SPECS/CUT SHEETS FOR |
| | ATS. |
| | PLEASE ALSO SUBMIT ALL SPECS/INFORMATION |
| | ON DC SYSTEM PROPOSED. |
| | THIS EQUIPMENT |
| | |
| | 9)NOTE: PLEASE SEE PERMIT APPLICATION |
| | MENTIONS ADDRESS AS "OLD OKEECHOBEE" |
| | PLEASE KNOW AND SEE BLDG REVIEW |
| | COMMENTS, THIS SHOULD READ "OKEECHOBEE |
| | RD". |
| | PLEASE ALSO ADJUST ON PLANS/TITL BLOCK. |
| | |
| | |
| | PLEASE COMPLETELY REMOVE ANY OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |