| 2005-11-07 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)DECLARE THE OCCUPANCY FOR THIS |
| | IMPROVEMENT THE OCCUPANCY FOR THE |
| | ADJACENT TENANT. |
| | |
| | 3.)THE BUILDING IS REQUIRED TO BE |
| | ACCESSIBLE.THERE ARE EXCEPTIONS IN THE |
| | CODE RELATED TO VERTICAL ACCESSIBILITY |
| | OR IN CASES WHERE IT IS STRUCTURALLY |
| | IMPRACTICABLE, BUT THESE EXCEPTIONS DO |
| | NOT APPLY.SEE FBC11-4.1.1(3), AREAS |
| | USED ONLY BY EMPLOYEES AS WORK AREAS. |
| | |
| | 4.)SHOW ACCESSIBLE ROUTE, |
| | FBC11-4.1.2(1). |
| | |
| | 5.)THE BATHROOM IS TO BE ACCESSIBLE. |
| | PROVIDE ALL DETAILS INCLUDING ALL |
| | DIMENSIONS.FBC11. |
| | |
| | 6.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF |
| | EGRESS SHALL BE PROVIDED IN THE SAME |
| | NUMBER AS REQUIRED FOR EXITS BY LOCAL |
| | BUILDING/LIFE SAFETY REGULATIONS.IT |
| | APPEARS THAT ONLY THE FRONT DOOR IS AN |
| | ACCESSIBLE EXIT.THE OTHER TWO APPEAR |
| | TO HAVE A LANDING OUTSIDE THE DOOR. |
| | |
| | 7.)FOR THE EXISTING 2 HOUR WALL, |
| | PROVIDE AN APPROVED ASSEMBLY OR |
| | CALCULATED FIRE RESISTANCE, FBC7. |
| | |
| | 8.)FOR THE INFILL FOR THE 2 HOUR WALL, |
| | PROVIDE AN APPROVED ASSEMBLY OR |
| | CALCULATED FIRE RESISTANCE, FBC7. |