| 2006-12-28 13:00:01 | CONTRACTOR INFORMATION | | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL INSPECTION. | | | THE SUBMITTED GAS RISER DIAGRAM CAN'T BE A REVISION | | | BECAUSE THERE IS NO GAS PERMIT. | | | | | | PLEASE NOTE THAT THE SUBMITTED GAS RISER DIAGRAM IS NOT | | | SIZED CORRECTLY PER THE FOLLOWING TABLES. | | | A} NFPA (ONLINE) TABLE 6.2(B) SCHEDULE 40 METALLIC PIPE | | | BECAUSE FBC-2004 FUEL GAS TABLE, 402.4 (2) ONLY GOES TO | | | 200'. | | | B} NFPA (ONLINE) TABLE 6.2(S) POLYETHYLENE PLASTIC PIPE | | | BECAUSE FBC-2004 FUEL GAS TABLE, 402.4 (20) ONLY GOES | | | TO 200'. | | | C} FBC-2004 FUEL GAS TABLE 402.4 (14) CSST. | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|