| Date |
Text |
| 2006-11-30 08:41:19 | REVISION UNSAT |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PLEASE NOTE THAT A SEPERATE GEN/RES PERMIT IS |
| | REQUIRED FOR THE GENERATOR AND THAT A GAS PERMIT CAN |
| | NOT BE ISSUED UNTIL ONE HAS BEEN APPLIED FOR AND |
| | ZONING, ELECTRICAL AND GAS HAS APPROVED THE GENERATOR |
| | LOCATION. OR YOU CAN INDICATE ON THE DRAWINGS THAT THE |
| | GENERATOR IS A "FUTURE" GENERATOR. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| | LENGTHS INDICATED ON THE GAS RISER DIAGRAM ON SHEET |
| | A-3. |
| | |
| | 3. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON |
| | SHEET A-3 GAS RISER DIAGRAM. |
| | |
| | 4.PLEASE INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON SHEET A-3 GAS |
| | RISER DIAGRAM. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: NEED MANUFACTURER SHEETS OF MP REGULATORS IF GAS |
| | SYSTEM IS 2PSI. ALSO NEED MANUFACTURER SHEETS AND |
| | INSTALLATION INSTRUCTIONS ON GENERATOR TO VERIFY BTU |
| | LOAD AND MINIMUM INSTALLATION CLEARENCES TO |
| | STRUCTURES. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |