| Plan Review Notes For Permit 05090030 |
| Permit Number |
05090030 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-16 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLANS MUST CONTAIN THE PRINTED NAME | | | AND SIGNATURE OF THE DESIGNER PER | | | 104.2.1.FBC | | | | | | 2} TWO SETS OF PLANS ARE TO BE SUBMITTED | | | FOR REVIEW PER 104.2.1.FBC | | | | | | 3} THE TRNSFER SWITCH MUST BE SERVICE | | | RATED OR MUST HAVE A RATED DISCONNECT | | | AHEAD (GENERATOR SIDE) OF IT | | | ELECTRICALLY. | | | | | | 4} PLEASE SUBMIT A SITE PLAN INDICATING | | | THE LOCATION OF ALL SERVICE AND | | | GENERATOR EQUIPMENT SO THAT COMPLIANCE | | | WITH 225.31 THROUGH 225.37 CAN BE | | | REVIEWED. | | | | | | 5} INDICATE THE FUEL TYPE PROPOSED AS | | | PRIME MOVER. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|