| 2005-09-09 00:00:00 | *** UNSAT **** |
| | |
| | 1)NOTE: |
| | PLEASE SEE 230.72 FOR GROUPING OF MAINS. |
| | PLEASE CLARIFY IF EXSITING MCB PANEL IS |
| | LOCATED IMMEDIATELY AJACENT/CLOSE |
| | PROXIMITY TO EXISTING PANELS. |
| | PLEASE SEE 225.31 FOR DISCONNECTING |
| | MEANS REQUIRED, GROUPED PER 225.34 AND |
| | RATED FOR SERVICE EQUIPMENT PER 225.36 |
| | PLEASE SEE NO SPECS/MANUFACTURE CUT |
| | SHEETS WERE SUBMITTED FOR ATS. |
| | PLEASE SEE THE REQUIRED DISCONNECT FROM |
| | GEN IS LOCATED ON THE OTHER SIDE OF |
| | HOUSE, WHICH DOES NOT GROUP MAINS. |
| | |
| | 2)NOTE: |
| | |
| | 3)NOTE: |
| | |
| | 4)NOTE: PLEASE SEELOAD CALCULATIONS |
| | SUBMITTED. PLEASE SEE 220.31B, NO |
| | DERATING MAY BE TAKEN FOR AHU/HEAT. |
| | PLEASE SEE IS IT PERMITTED TO "LOAD |
| | SHED" HEAT LOADS FROM A/C SYSTEMS |
| | THROUGH LV CONTACTORS FROM GEN OR ATS. |
| | 220.31,702.5, 90.4,700.5 |
| | PLEASE SEE 700.58, WHICH PERMIT LOAD |
| | SHEDDING. PLEASE PROVIDE DETAIL IS ANY |
| | OF THE LV CONTACTS PROVIDE BY ATS OR GEN |
| | WILL BE USED TO INTERUPT ONE OR MORE |
| | HEAT CONTROL WIRES. |
| | |
| | 5)NOTE: |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |