| 2005-09-09 00:00:00 | *** UNSAT **** |
| | |
| | 1)NOTE: PLEASE SEE MAIN DISCONNECT IS |
| | REQUIRED TO MANUAL AND LOCATED ON THE |
| | OUTSIDE OF SERVICE EQUIPMENT. |
| | 230.76,230.79 |
| | PLEASE SEE 230.72 FOR GROUPING OF MAINS. |
| | PLEASE CLARIFY IF EXSITING MCB PANEL IS |
| | LOCATED IMMEDIATELY AJACENT/CLOSE |
| | PROXIMITY TO EXISTING PANELS. |
| | PLEASE SEE 225.31 FOR DISCONNECTING |
| | MEANS REQUIRED, GROUPED PER 225.34 AND |
| | RATED FOR SERVICE EQUIPMENT PER 225.36 |
| | PLEASE SEE NO SPECS/MANUFACTURE CUT |
| | SHEETS WERE SUBMITTED FOR ATS. |
| | |
| | 2)NOTE: PLEASE SEE RISER INDICATES AN |
| | "EQUIPMENT GROUNDING" CONDUCTOR FROM |
| | METER TO MAIN. 250.6, 250.24 |
| | PLEASE SEE AN EQUIPMENT GRND IS ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS |
| | DOES NOT INDICATE LOCATION OF ATS, |
| | EXISTING MAINS, OR EXISITNG PANELS. |
| | ARE EXISTING PANELS MCB? |
| | |
| | |
| | 4)NOTE: PLEASE SEELOAD CALCULATIONS |
| | SUBMITTED. PLEASE SEE 220.31B, NO |
| | DERATING MAY BE TAKEN FOR AHU/HEAT. |
| | PLEASE SEE IS IT PERMITTED TO "LOAD |
| | SHED" HEAT LOADS FROM A/C SYSTEMS |
| | THROUGH LV CONTACTORS FROM GEN OR ATS. |
| | 220.31,702.5, 90.4,700.5 |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE VERFIY 3 OVENS SHOWN ON |
| | SERVICE PANELS?? THIS IS OK, JUST A |
| | NOTE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |