| Plan Review Notes For Permit 05082056 |
| Permit Number |
05082056 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-09 00:00:00 | *** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE MAIN DISCONNECT IS | | | REQUIRED TO MANUAL AND LOCATED ON THE | | | OUTSIDE OF SERVICE EQUIPMENT. | | | 230.76,230.79 | | | PLEASE SEE 230.72 FOR GROUPING OF MAINS. | | | PLEASE CLARIFY IF EXSITING MCB PANEL IS | | | LOCATED IMMEDIATELY AJACENT/CLOSE | | | PROXIMITYTO NEW ATS. | | | MAIN LOATED INSIDE ATS MAY NOT | | | CONSIDERED THE MAIN FOR SERVICE. | | | 230.70A1 | | | | | | 2)NOTE: PLEASE SEE RISER INDICATES AN | | | "EQUIPMENT GROUNDING" CONDUCTOR FROM | | | METER TO MAIN. 250.6, 250.24 | | | PLEASE SEE AN EQUIPMENT GRND IS ONLY | | | INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | | | | | | | 3)NOTE: | | | | | | 4)NOTE: PLEASE SEELOAD CALCULATIONS | | | SUBMITTEDFOR REVIEW DOES NOT SEEM TO | | | INCLUDE ALL CIRCUITS DEDICATED ETC ON | | | ENTIRE HOUSE PANEL. | | | PLEASE INLCUDE ANY MOTOR LOADS, FRIG, | | | WASHER ETC. | | | 220,702.5,215.5 | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|