Plan Review Notes
Plan Review Notes For Permit 05082056
Permit Number 05082056
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-09 00:00:00*** UNSAT ****
  
 1)NOTE: PLEASE SEE MAIN DISCONNECT IS
 REQUIRED TO MANUAL AND LOCATED ON THE
 OUTSIDE OF SERVICE EQUIPMENT.
 230.76,230.79
 PLEASE SEE 230.72 FOR GROUPING OF MAINS.
 PLEASE CLARIFY IF EXSITING MCB PANEL IS
 LOCATED IMMEDIATELY AJACENT/CLOSE
 PROXIMITYTO NEW ATS.
 MAIN LOATED INSIDE ATS MAY NOT
 CONSIDERED THE MAIN FOR SERVICE.
 230.70A1
  
 2)NOTE: PLEASE SEE RISER INDICATES AN
 "EQUIPMENT GROUNDING" CONDUCTOR FROM
 METER TO MAIN. 250.6, 250.24
 PLEASE SEE AN EQUIPMENT GRND IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
  
 3)NOTE:
  
 4)NOTE: PLEASE SEELOAD CALCULATIONS
 SUBMITTEDFOR REVIEW DOES NOT SEEM TO
 INCLUDE ALL CIRCUITS DEDICATED ETC ON
 ENTIRE HOUSE PANEL.
 PLEASE INLCUDE ANY MOTOR LOADS, FRIG,
 WASHER ETC.
 220,702.5,215.5
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  