2006-02-03 00:00:00*******UNSAT ******
  
  
 1)NOTE: PLEASE SEE OWNER BUILDER
 DISCLOSURE STATEMENT SUBMITTED IS NOW A
 PHOTOCOPY OF ORIGINAL,
 PLEASE KNOW WE ARE REQUIRED TO HAVE THE
 ORIGINAL , NOTORIZED STATEMENT.
 FS 489.
  
 2)NOTE: PLEASE SEE RISER SUBMITTED IS
 STILL SHOWING THE CHANGING OF WHAT IS A
 LISTED PIECE OF EQUIPMENT. PLEASE SEE
 FEED TO TRANSFER SWITCH MAY COME FROM
 THE LOAD SIDE OF THE METER/MAIN, HOWEVER
 PLEASE VERIFY AS THESPACES/CIRCUITING
 IN A METER/MAIN COMBO DO NOT SEEM TO BE
 ENOUGH?
 215.5
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE
 SUBMITTED DOES NOT CORRELATE WITH THE
 LOAD CALCULATIONS SUBMITTED. PLEASE
 VERIFY OF THERE IS ANOTHER PANEL.
 215.5
  
 4)NOTE: PLEASE INDICATE ON LOAD
 CALCULATIONS AND SUBMIT DETAIL FOR THE
 LOAD SHEDDING OF A/C. A/C IS SHOWN AS
 BEING OMITTED FROM PLANS??
 NEC DOES PERMIT LOAD SHEDDING, HOWEVER
 THIS NEEDS TO BE SHOWN.
 215.5
  
 5)NOTE: PLEASE SUBMIT TWO SETS OF PLANS,
 SPEC ETC.ONLY ONE SUBMITTED. (TWO
 SURVEYS WERE SUBMITTED .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]