| Plan Review Notes For Permit 05082009 |
| Permit Number |
05082009 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-03 00:00:00 | *******UNSAT ****** | | | | | | | | | 1)NOTE: PLEASE SEE OWNER BUILDER | | | DISCLOSURE STATEMENT SUBMITTED IS NOW A | | | PHOTOCOPY OF ORIGINAL, | | | PLEASE KNOW WE ARE REQUIRED TO HAVE THE | | | ORIGINAL , NOTORIZED STATEMENT. | | | FS 489. | | | | | | 2)NOTE: PLEASE SEE RISER SUBMITTED IS | | | STILL SHOWING THE CHANGING OF WHAT IS A | | | LISTED PIECE OF EQUIPMENT. PLEASE SEE | | | FEED TO TRANSFER SWITCH MAY COME FROM | | | THE LOAD SIDE OF THE METER/MAIN, HOWEVER | | | PLEASE VERIFY AS THESPACES/CIRCUITING | | | IN A METER/MAIN COMBO DO NOT SEEM TO BE | | | ENOUGH? | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULE | | | SUBMITTED DOES NOT CORRELATE WITH THE | | | LOAD CALCULATIONS SUBMITTED. PLEASE | | | VERIFY OF THERE IS ANOTHER PANEL. | | | 215.5 | | | | | | 4)NOTE: PLEASE INDICATE ON LOAD | | | CALCULATIONS AND SUBMIT DETAIL FOR THE | | | LOAD SHEDDING OF A/C. A/C IS SHOWN AS | | | BEING OMITTED FROM PLANS?? | | | NEC DOES PERMIT LOAD SHEDDING, HOWEVER | | | THIS NEEDS TO BE SHOWN. | | | 215.5 | | | | | | 5)NOTE: PLEASE SUBMIT TWO SETS OF PLANS, | | | SPEC ETC.ONLY ONE SUBMITTED. (TWO | | | SURVEYS WERE SUBMITTED . | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6717 | | | [email protected] |
|