| 2005-09-09 00:00:00 | *** UNSAT **** |
| | |
| | 1)NOTE: PLEASE SEE SERVICE RISER SHOWN |
| | IS NOT CLEAR WHERE THE POWER IS GOING TO |
| | TRANSFER?? APPEARS TO SHOW FEED FROM A |
| | METER/MAIN PANEL TO A MAIN DISC AND TO |
| | ATS AND BACK TO METER MAIN COMBO? |
| | PLEASE SHOW WHERE FAIL SAFE OPERATION IS |
| | LOCATED.700.6 |
| | NO MEANS OF OCP IS SHOWN AT MAIN/METER?? |
| | I |
| | PLEASE SEE 230.72 FOR GROUPING OF MAINS. |
| | PLEASE CLARIFY IF EXSITING MCB PANEL IS |
| | LOCATED IMMEDIATELY AJACENT/CLOSE |
| | PROXIMITYTO NEW ATS. |
| | MAIN LOATED INSIDE ATS MAY NOT |
| | CONSIDERED THE MAIN FOR SERVICE. |
| | 230.70A1 |
| | |
| | |
| | 2)NOTE: PLEASE SEE RISER MISSING ANY |
| | "EQUIPMENT GROUNDING" CONDUCTORS WHERE |
| | REQUIRED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | 250.24,250.110,250.122 |
| | |
| | 3)NOTE: PLEASE SEE NO LOAD CALCULATIONS |
| | WERE SUBMITTEDFOR REVIEW OF LOADS. |
| | 220,702.5 |
| | PLEASE SEE GEN SHALL BE SIZED FOR ENTIRE |
| | SERVICE AS SHOWN. |
| | IF AN EMERGENCY SUB PANEL IS BEING |
| | INSTALLED, PLEAS INDICATE. |
| | |
| | 4)NOTE: PLEASE SUBMIT THE MANUFACTURE |
| | CUT SHEETS WHICH INDICAT ALL LISTINGS OF |
| | EQUIPMENT. |
| | PLEASE SEE 225.36 WHICH REQUIRES THE |
| | DISCONNECTING MEANS TO BE RATED AS |
| | SERVICE EQUIPMENT. |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| | REQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS. |
| | |
| | 7)NOTE; PLEASE SEE FBC 104.6.5 |
| | ADMINISTRATIVE CODE, WHICH REQUIRES THE |
| | APPLIED VALUE TO INCLUDE ALL LABOR AND |
| | MATERIALS. |
| | VALUE ON APPLICATION SEEM TO ONLY |
| | INDICATE THE VALUE OF EQUIPMENT AND NOT |
| | THE INSTALLATION. |
| | PLEASE VERIFY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |