2006-05-30 00:00:00REVISION DENIED;
 1. FLOOR DRAINS FOR DENTAL CHAIRS TO BE
 A MINIMUM OF 2" SEE FBC-2004 PLUMBING
 TABLE 709.1.
 2.SHUTOFF VALVES FOR COMP. AIR REQUIRED
 PER NFPA 99C SEC.5.3.4.1(C).
 PLUMBING PLAN REVIEW BY;