| Plan Review Notes For Permit 05082001 |
| Permit Number |
05082001 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-14 00:00:00 | DENIED; | | | 1. STAFF LOUNGE SINK TO COMPLY WITH FBC | | | 2001 CHAPTER 11 SEC. 11-4.24.1 THRU | | | 11-4.24.7. SHOW DETAIL. | | | 2.FBC 2001 PLUMBING TABLE 403.1 MINIMUM | | | FACILITIES REQUIRES A DRINKING FOUNTAIN. | | | 3.PLEASE SUBMIT MANUFACTOR'S INFORMATION | | | FOR, AIR COMPRESSOR, VACUUM PUMP, AND | | | MODEL TRIMMER ASSEMBLY. | | | MED-GAS | | | 1.VACUUM PIPING TO COMPLY WITH NFPA 99C | | | SEC. 4-5.2.2.1 CLEANOUT FACILITIES | | | REQUIRED. SHOW ON DRAWING. | | | 2.VACUUM PUMP EXHAUST IS REQUIRED TO GO | | | TO THE OUTSIDE. PLEASE SHOW LOCATION AND | | | SIZE OF PIPE. | | | 3.(ADD TO NOTES) PLUMBING CONTRACTOR | | | REQUIRED TO BE LICENSED TO INSTALL | | | MEDICAL GAS. SEPARATE PERMIT REQUIRED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | | | | | | | | | | | | | | | | |
|