Plan Review Notes
Plan Review Notes For Permit 05082001
Permit Number 05082001
Review Stop P
Sequence Number 1
Notes
Date Text
2005-09-14 00:00:00DENIED;
 1. STAFF LOUNGE SINK TO COMPLY WITH FBC
 2001 CHAPTER 11 SEC. 11-4.24.1 THRU
 11-4.24.7. SHOW DETAIL.
 2.FBC 2001 PLUMBING TABLE 403.1 MINIMUM
 FACILITIES REQUIRES A DRINKING FOUNTAIN.
 3.PLEASE SUBMIT MANUFACTOR'S INFORMATION
 FOR, AIR COMPRESSOR, VACUUM PUMP, AND
 MODEL TRIMMER ASSEMBLY.
 MED-GAS
 1.VACUUM PIPING TO COMPLY WITH NFPA 99C
 SEC. 4-5.2.2.1 CLEANOUT FACILITIES
 REQUIRED. SHOW ON DRAWING.
 2.VACUUM PUMP EXHAUST IS REQUIRED TO GO
 TO THE OUTSIDE. PLEASE SHOW LOCATION AND
 SIZE OF PIPE.
 3.(ADD TO NOTES) PLUMBING CONTRACTOR
 REQUIRED TO BE LICENSED TO INSTALL
 MEDICAL GAS. SEPARATE PERMIT REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  
  
  
  
  
  