2005-09-02 00:00:00*********** UNSAT *************
  
 PLEASE SEE PLANS ARE SUBMITTED FOR "PLAN
 REVEW" ONLY AND HAVE NOT BEEN SUBMITTED
 FORPERMIT.
  
  
  
 1)NOTE: PLEASE SEE SEE PANEL "A" WHICH
 INDICATES FEEDERS AS 4 # 13'S.
 THIS APPEARS TO BE A MISPRINT.
 PLEASE ADJUST AND CORRELATE WITH FEEDERS
 INDICATED ON RISER.
  
 2)NOTE: PLEASE SEE PANEL "B" INDICATES
 LOAD FOR PANEL"A" AS BEING 10A'S?
 PLEASE SEE PANEL "A" LOAD IS SHOWN MUCH
 HIGHER.
  
 3)NOTE: PLEASE CLARIFY IF NEW OR EXSITNG
 RECEPT IS AVAILABLE FOR ROOFTOP A/C
 UNIT.
 210.63,210.8
  
 4)NOTE: PLEASE BE SURE THE TITLE BLOCK
 FOR ARCHITECT/FIRM CONTAINS THE PRINTED
 NAME AND LICENSE # OF ARCHITECT. FAC
 61G1-16.004,
 PLEASE SEE THIS IR REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLU INSERT NEW REVISED SHEETS INTO
 COMPLETER SETS FOR REVIEW AND STAMPING.