2005-09-06 00:00:00****CORRECTIONS****
 ****PLAN CHECK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC103.1.2.
  
 3.)PLEASE READ FAC61G1-16.003, 004.
 THE SEAL IS TO BE DATED.
  
 4.)THE STAFF LOUNGE SINK IS TO COMPLY
 WITH ALL REQUIREMENTS OF FBC11-4.24.
 PROVIDE A DETAIL.NOTE THAT THE DOOR
 SWINGS INTO THE CLEAR FLOOR SPACE.
  
 5.)SHEET A2 WEST PORTION SHOWS A NEW
 LOBBY, IS THIS A PART OF THIS PERMIT?
  
 6.)PROVIDE A DETAIL FOR THE 1 HOUR
 INFILL WALL, EITHER A LISTED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FBC709.
  