Plan Review Notes
Plan Review Notes For Permit 05081999
Permit Number 05081999
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-10 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE MISSING REQUIRED NEW
 FOOTER STEEL TO ALSO BE PART OF THE NEW
 GROUNDING ELECTRODE SYSTEM FOR NEW
 SERVICE.
 PLEASE SEE RISER SHOWS ONLY COLD WATER
 PIPE? NO GRND ROD(S) ETC. 250.50.
  
 2)NOTE: PLEASE SEE PLANS SHOWS A NEW
 STACKABLE WASHER/DRYER, HOWEVER THIS IS
 NOT LISTED ON PANEL SCHEDULE OR LOAD
 CALCULATIONS.
 215.5,220.31
 PLEASE SHOW OCP, AWG AND KW RATING.
 240.4,310.16
  
 3)NOTE: PLEASE SEE 2002 NEC 210.12 WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 OUTLETS IN BEDRMS. SD, LTS, FANS,
 RECEPTS, ETC.
  
 4)NOTE: PLEASE SEE FBC CHAPTER
 34,3401.7.1.2.1 FOR ADDITIONS TO EXSITNG
 DWELLING IN R-3 OCCUPANCIES.
 PLEASE SEE ADDTIONS OVER 25% TO EXISTING
 DWELLING.
 PLEASE SHOW EITHER EXISTING OR NEW SMOKE
 DETECTORS WHICH MEET NFPA-72 11.5.1.1 .
 THESE SHALL BE WIRED IN-LINE WITH NEW
 ADDTION SD'S.
 PLEASE ALSO SHOW ALL NEW OR EXSITNG
 RECEPTS IN LOCATIONS WHICH ARE REQUIRED
 TO BE GFI/GFI PROTECTED. (KITCHENS,
 BATHS, OUTSIDE, ETC. 210.8A1-7).
  
 5)NOTE: PLEASE INCLUDE NEW SERVICE
 ENTRANCE CONDUCTORS AND RISER SIZE AND
 TYPE.; PLANS NOTES THIS BY FPL, HOWEVER
 FPL ONLY IS RESPONSIBLE FOR THE SERVICE
 DROP UP TO THE WEATHER-HEAD.
 310.15B6,240.4
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 1)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NUMBER ON A- SHEETS.
 THIS IS NOT FOR ELECTRICAL SHEETS.
 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]