| 2005-09-10 00:00:00 | ********* UNSAT ********** |
| | |
| | |
| | 1)NOTE: PLEASE SEE MISSING REQUIRED NEW |
| | FOOTER STEEL TO ALSO BE PART OF THE NEW |
| | GROUNDING ELECTRODE SYSTEM FOR NEW |
| | SERVICE. |
| | PLEASE SEE RISER SHOWS ONLY COLD WATER |
| | PIPE? NO GRND ROD(S) ETC. 250.50. |
| | |
| | 2)NOTE: PLEASE SEE PLANS SHOWS A NEW |
| | STACKABLE WASHER/DRYER, HOWEVER THIS IS |
| | NOT LISTED ON PANEL SCHEDULE OR LOAD |
| | CALCULATIONS. |
| | 215.5,220.31 |
| | PLEASE SHOW OCP, AWG AND KW RATING. |
| | 240.4,310.16 |
| | |
| | 3)NOTE: PLEASE SEE 2002 NEC 210.12 WHICH |
| | REQUIRES ARC FAULT PROTECTION FOR ALL |
| | OUTLETS IN BEDRMS. SD, LTS, FANS, |
| | RECEPTS, ETC. |
| | |
| | 4)NOTE: PLEASE SEE FBC CHAPTER |
| | 34,3401.7.1.2.1 FOR ADDITIONS TO EXSITNG |
| | DWELLING IN R-3 OCCUPANCIES. |
| | PLEASE SEE ADDTIONS OVER 25% TO EXISTING |
| | DWELLING. |
| | PLEASE SHOW EITHER EXISTING OR NEW SMOKE |
| | DETECTORS WHICH MEET NFPA-72 11.5.1.1 . |
| | THESE SHALL BE WIRED IN-LINE WITH NEW |
| | ADDTION SD'S. |
| | PLEASE ALSO SHOW ALL NEW OR EXSITNG |
| | RECEPTS IN LOCATIONS WHICH ARE REQUIRED |
| | TO BE GFI/GFI PROTECTED. (KITCHENS, |
| | BATHS, OUTSIDE, ETC. 210.8A1-7). |
| | |
| | 5)NOTE: PLEASE INCLUDE NEW SERVICE |
| | ENTRANCE CONDUCTORS AND RISER SIZE AND |
| | TYPE.; PLANS NOTES THIS BY FPL, HOWEVER |
| | FPL ONLY IS RESPONSIBLE FOR THE SERVICE |
| | DROP UP TO THE WEATHER-HEAD. |
| | 310.15B6,240.4 |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | 1)NOTE: PLEASE SEE MISSING CERTIFICATE |
| | OF AUTHORIZATION NUMBER ON A- SHEETS. |
| | THIS IS NOT FOR ELECTRICAL SHEETS. |
| | 61G15-23.002, FS 471.023 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |