Plan Review Notes
Plan Review Notes For Permit 05081995
Permit Number 05081995
Review Stop Z
Sequence Number 3
Notes
Date Text
2006-06-19 00:00:00PLANNING DEPARTMENT RESUBMITTAL
 NADINE BIGBY, PLANNER
 RE-SUBMITTAL 6/29/06 2ND NOTATION
  
 RE-SUBMITTAL FOR PALM TRAN PERMIT NO.
 05081995 AT 3201 ELECTRONICS WAY.
 PER OUR MEETING ON FRIDAY, JUNE 16, 2006
 PLEASE FIND A BRIEF EXPLANATION OF THE
 REQUIREMENTS STILL PENDING FOR APPROVAL.
 THE FOLLOWING ITEMS SHALL BE ADDRESSED:
  
 1.PROVIDE A BETTER DETAIL OF THE AREA,
 NOT AN ENLARGEMENT.THIS CAN BE
 ACCOMPLISHED BY PROVIDING A DIGITAL COPY
 AND/OR A REDUCE COPY OF THE SURVEY.THE
 SURVEY SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/
 HEDGES AROUND GENERATOR/ FUEL TANK, AND
 SETBACK DISTANCE.
  
 B. PURSUANT TO SECTION 94-443(B)(1)
 BUFFERING:
 LANDSCAPE BUFFERING FOR INDUSTRIAL USES,
 THE BUFFER STRIP SHALL BE TEN FEET WIDE
 ALONG THE EDGE OF PROPERTY WHEN ADJACENT
 TO A PUBLIC THOROUGHFARE AND AT LEAST 5
 FEET WIDE ALONG THE EDGE OF PROPERTY
 WHEN ADJACENT TO NONRESIDENTIAL ZONING
 DISTRICTS.
  
 2.PURSUANT TO SECTION 94-444(B) OPEN
 SPACE STANDARDS:
 (B) FUEL OR OIL OR PROPANE TANKS,
 GENERATORS SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND
 STEEL.WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A FOUR-SIDED ENCLOSURE WITH
 AN OBSCURING GATE MAY BE REQUIRED AS A
 CONDITION FOR SITE PLAN APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL
 TANK INCLUDING ROOFTOP EXHAUST (TANK)
 AND GENERATOR.
  
 3. PURSUANT TO SECTION 94-305(B)(4)
 SETBACKS
 (B)(4) SETBACK ENCROACHMENT: MECHANICAL
 EQUIPMENT SHALL NOT PROJECT MORE THAN 4
 FEET INTO A SETBACK.
  
 IF YOU NEED MORE INFORMATION, I CAN BE
 REACHED AT 822-1435.
  
 THANK YOU
2006-06-13 00:00:00PLANNING AND ZONING: FAILED
  
 RESUBMITTAL
 THE FOLLOWING ITEMS WERE NOT ADDRESSED:
  
 1.PROVIDE A BETTER DETAIL OF THE AREA,
 NOT AN ENLARGEMENT.
  
 2.PURSUANT TO SECTION 94-444(B)FUEL OIL
 OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED.
  
 3. PURSUANT TO SECTION 94-305(B)(4)
 MECHANICAL EQUIPMENT MAY NOT PROJECT
 MORE THAN FOUR FEET INTO SETBACK.
  
 REVIEWED BY: NADINE BIGBY, PLANNER
  
 IF YOU NEED MORE INFORMATION, I CAN BE
 REACHED AT 822-1435.
2006-06-06 00:00:00THE FOLLOWING COMMENTS WERE ORIGINALLY
 ENTERED BY NADINE BIGBY UNDER THE
 GEN-ELEC (ELECTRICAL) PERMIT FOR THE
 GENERATOR:
  
  
 PLANNING AND ZONING DEPARTMENT: FAILED
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED:
  
 1. PROVIDE A BETTER DETAIL OF THE AREA
 ON THE SITE PLAN.
  
 2. SCREENING IS REQUIRED AROUND FUEL
 TANK AND GENERATOR.
  
 REVIEWED BY NADINE BIGBY, PLANNER
  
 IF YOU NEED MORE INFORMATION, I CAN BE
 REACHED AT (561)822-1435.