| Plan Review Notes For Permit 05081995 |
| Permit Number |
05081995 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-13 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.PLEASE PROVIDE PLANS INDICATING | | | THE FOLLOWING: | | | | | | - PIPE MATERIAL, SIZE, AND LAYOUT. | | | - INDICATE SUPPLY, RETURN, & VENT | | | - INDICATE PIPE SUPPORT. | | | - INDICATE SUPPORT ANCHORING | | | - INDICATE ALL VALVES | | | | | | SHOW COMPLIANCE WITH 2004 FMC CHAPTER | | | 13, NFPA 110, NFPA 30, NFPA 37, NFPA 70. | | | | | | ADDITIONAL PERMIT REQUIRED FOR FUEL TANK | | | & PIPING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|