Plan Review Notes
Plan Review Notes For Permit 05081995
Permit Number 05081995
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-07 00:00:00******* UNSAT 3RD REVIEW *******
  
 ** PLEASE SEE NOTES FROM PREVIOUS
 REVIEW(S) WHICH STILL REMAIN.
  
 1) NOTE: PLEASE SEE NOTES ADDED TO RISER
 THAT MENTIONS THE NEW SERVICE ENTRANCE
 RATED MAIN/ATS SWITCHES TO MEET 230.76,
 230.79, ETC HOWEVER PLEASE SEE THE SPECS
 SUBMITTED DO NOT INDICATE THIS.?
 PLEASE KNOW THE FIRST MEANS OF
 DISCONNECT FOR THE SERVICE ARE NOW THESE
 NEW PEICES OF EQUIPMENT SHOWN AND FFROM
 THE INFORMATION SUBMITTED, THIS CAN BE
 NOT VERIFIED
 PLEASE SEE 225.31 REQUIRES A MEANS OF
 DISCONNECT FOR THE FEEDERS COMING FROM
 THE GENERATOR UP AND INTO THE BUILDING
 AT THE NEAREST POINT OF ENTRANCE. PLEASE
 SEE THESE APPEAR TO BE ROUTED INSIDE THE
 BUILDING? ONLY MENTIONS "HIGH ON THE
 WALL". IS THIS OUTSIDE OR INSIDE?PLEASE
 SEE 230.6.
  
 2) NOTE: PLEASE SEE THE RISER DIAGRAM
 DOES NOT CORRELATE FOR THE NEW SERVICE
 ENTRANCE RATED ATS/MAIN(S). PLEASE SEE
 NOTE #3 ON RISER MENTIONS THE ATS/MAIN
 BEING 4-POLE AS NEEDED AND REQUIRED ,
 HOWEVER PLEASE SEE THE RISER IS STILL
 SHOWING THESE AS 3-POLE?
 PLEASE SEE THE COVER SHEETS ON THE
 GENERATOR/ ATS SUBMITTIALS EVEN MENTIONS
 FROM THE DESIGN FIRM THAT THE ATS
 SUMMARY IS NOT CORRECT. PLEASE SEE THE
 ATS SUMMARY INDICATES A 3-POLE ATS.
 PLEASE KNOW, ALL SPECS, RISER AND NOTES
 SHALL CORRELATE.
  
 3) NOTE: PLEASE SEE RISER STILL
 INDICATES "GFI" PROTECTION FOR THESE
 ATS/ MAINS. PLEASE SEE 230.95,240.13
 ETC. THIS CLASS OF PROTECTION IS NOT
 GFI. PLEASE KNOW THERE IS A SUBSTANTIAL
 DIFFERENCE BETWEEN GFI AND GF
 PROTECTION. PLEASE ADJUST RISER IN ALL
 LOCATION.
  
 4) NOTE: PLEASE SEE A NOTICE ATTACHED
 PER FS 553.80(2)(B) IS NOW GIVEN WITH
 RESPECT TO PLANS AND REPEAT COMMENTS.
 THIS IS ONLY A NOTICE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 COMMENTS , PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE SO THAT THESE
 ITEMS CAN BE GONE OVER. PLEASE KNOW,
 CONTACT TO MYSELFHAS NOT BEEN DONE AS
 OF TODAY'S DATE AND THIS REVIEW.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  