| 2006-06-07 00:00:00 | ******* UNSAT 3RD REVIEW ******* |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS |
| | REVIEW(S) WHICH STILL REMAIN. |
| | |
| | 1) NOTE: PLEASE SEE NOTES ADDED TO RISER |
| | THAT MENTIONS THE NEW SERVICE ENTRANCE |
| | RATED MAIN/ATS SWITCHES TO MEET 230.76, |
| | 230.79, ETC HOWEVER PLEASE SEE THE SPECS |
| | SUBMITTED DO NOT INDICATE THIS.? |
| | PLEASE KNOW THE FIRST MEANS OF |
| | DISCONNECT FOR THE SERVICE ARE NOW THESE |
| | NEW PEICES OF EQUIPMENT SHOWN AND FFROM |
| | THE INFORMATION SUBMITTED, THIS CAN BE |
| | NOT VERIFIED |
| | PLEASE SEE 225.31 REQUIRES A MEANS OF |
| | DISCONNECT FOR THE FEEDERS COMING FROM |
| | THE GENERATOR UP AND INTO THE BUILDING |
| | AT THE NEAREST POINT OF ENTRANCE. PLEASE |
| | SEE THESE APPEAR TO BE ROUTED INSIDE THE |
| | BUILDING? ONLY MENTIONS "HIGH ON THE |
| | WALL". IS THIS OUTSIDE OR INSIDE?PLEASE |
| | SEE 230.6. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER DIAGRAM |
| | DOES NOT CORRELATE FOR THE NEW SERVICE |
| | ENTRANCE RATED ATS/MAIN(S). PLEASE SEE |
| | NOTE #3 ON RISER MENTIONS THE ATS/MAIN |
| | BEING 4-POLE AS NEEDED AND REQUIRED , |
| | HOWEVER PLEASE SEE THE RISER IS STILL |
| | SHOWING THESE AS 3-POLE? |
| | PLEASE SEE THE COVER SHEETS ON THE |
| | GENERATOR/ ATS SUBMITTIALS EVEN MENTIONS |
| | FROM THE DESIGN FIRM THAT THE ATS |
| | SUMMARY IS NOT CORRECT. PLEASE SEE THE |
| | ATS SUMMARY INDICATES A 3-POLE ATS. |
| | PLEASE KNOW, ALL SPECS, RISER AND NOTES |
| | SHALL CORRELATE. |
| | |
| | 3) NOTE: PLEASE SEE RISER STILL |
| | INDICATES "GFI" PROTECTION FOR THESE |
| | ATS/ MAINS. PLEASE SEE 230.95,240.13 |
| | ETC. THIS CLASS OF PROTECTION IS NOT |
| | GFI. PLEASE KNOW THERE IS A SUBSTANTIAL |
| | DIFFERENCE BETWEEN GFI AND GF |
| | PROTECTION. PLEASE ADJUST RISER IN ALL |
| | LOCATION. |
| | |
| | 4) NOTE: PLEASE SEE A NOTICE ATTACHED |
| | PER FS 553.80(2)(B) IS NOW GIVEN WITH |
| | RESPECT TO PLANS AND REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS , PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE SO THAT THESE |
| | ITEMS CAN BE GONE OVER. PLEASE KNOW, |
| | CONTACT TO MYSELFHAS NOT BEEN DONE AS |
| | OF TODAY'S DATE AND THIS REVIEW. |
| | |
| | |