| Plan Review Notes For Permit 05081995 |
| Permit Number |
05081995 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-02 00:00:00 | DENIED: | | | 1. ENGINEERED PLANS ARE REQURIED TO HAVE | | | A RAISED SEAL FS471.025 & FAC | | | 61G15-23.002.PLAN SHEET E-1 & E-2 ARE | | | NOT SEALED.SEE ALSO COMMETN #4 BY | | | DEWEY PALMER, ELECTRICAL PLANS EXAMINER. | | | | | | PER 2004 FMC 303.4, EQUIPMENT SHALL NOT | | | BE INSTALLED IN A LOCATION WHERE SUBJECT | | | TO MECHANICAL DAMAGE UNLESS PROTECTED BY | | | APPROVED BARRIERS. | | | | | | ADDITIONAL PERMIT REQUIRED FOR FUEL OIL | | | PIPING SHOW COMPLIANCE WITH 2001 NFPA 31 | | | WITH FUEL PIPING.PROVIDE PIPE SIZING, | | | MATERIAL, LAYOUT AND SUPPORT.PLEASE | | | PROVIDE PLANS WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|