2006-03-02 00:00:00DENIED:
 1. ENGINEERED PLANS ARE REQURIED TO HAVE
 A RAISED SEAL FS471.025 & FAC
 61G15-23.002.PLAN SHEET E-1 & E-2 ARE
 NOT SEALED.SEE ALSO COMMETN #4 BY
 DEWEY PALMER, ELECTRICAL PLANS EXAMINER.
  
 PER 2004 FMC 303.4, EQUIPMENT SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT
 TO MECHANICAL DAMAGE UNLESS PROTECTED BY
 APPROVED BARRIERS.
  
 ADDITIONAL PERMIT REQUIRED FOR FUEL OIL
 PIPING SHOW COMPLIANCE WITH 2001 NFPA 31
 WITH FUEL PIPING.PROVIDE PIPE SIZING,
 MATERIAL, LAYOUT AND SUPPORT.PLEASE
 PROVIDE PLANS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.