Plan Review Notes
Plan Review Notes For Permit 05081995
Permit Number 05081995
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-23 00:00:00**** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NEW COMMENTS AS
 INFORMATION FOR EQUIPMENT IS NOW BEING
 SUBMITTED FOR REVIEW.
  
 1)NOTE:
  
 2)NOTE: PLEASE SEE A NOTE ON PLANS
 MENTIONS ATS'S ARE TO HAVE A MANUAL
 MEANS OF DISCONNECT AND THAT MEANS OF
 DISCONNECT IS GOING TO BE ON THE OUTSIDE
 OF THE EQUIPMENT AND RATED FOR THE LOAD
 SERVED, (230.76,230.79 ETC), HOWEVER THE
 SPECS SUBMITTED DO NOT CONFIRM AND
 CORRELATE WITH THIS??
  
  
 3)NOTE: PLEASE SEE THE ATS'S ARE ALSO
 BEING SHOWN AS 3-POLE? PLEASE SEE SYSTEM
 IS SHOWING GFI, THIS SHOULD BE GF
 PROTECTED AS GFI IS FOR PERSONNEL
 PROTECTION.
 PLEASE SEE 230.95,240.13,700.7D,700.26
 AND NFPA-110 6.2.15
 PLEASE ALSO SEE THIS FOLLOWING TEXT
 TAKEN DIRECTLY FROM PAGE #5 FROM ASCO.
  
 "WHERE GROUND FAULTPROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE
 CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A
 CIRCUMSTANCE. THE SERVICE IS LARGER THAN
 1,000 AMPS. CONSEQUENTLY, GROUNDFAULT
 PROTECTION IS REQUIRED AT THE MAIN
 SERVICE DISCONNECT AT A MINIMUM. IF IT
 IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOTDISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS
 LOST."
 PLEASE SEE AS IT IS REVIEWED BY THIS
 OFFICE AND OTHER CONSULTATIONS, A 4-POLE
 ATS WOULD BE REQUIRED, THIS WOULD ALSO
 CREATE THE SEPARATELY DERIVED SYSTEM,
 AND PLEASE ADJUST THE GROUNDING
 ELECTRODE SYSTEM AT THE GEN ACCORDINGLY.
  
 4)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FS
 471.025 TO BE CLEAR AND VISABLE WIHT ALL
 SAID INFORMATION ON RIASED SEAL. PELASE
 SEE ONLY ONE SHEET FROM EACH SET IS
 VISABLE WITH THIS INFORMATION AND RAISED
 SEAL.
 PLEASE ALSO SEE 61G15-23.001 WHICH
 REQUIRES THE SEAL TO CONTAIN THE WORDING
 OF "LICENSE" AND NOT "CERTIFICATE"
 PLEASE KNOW, THIS WAS PASSED FEB 04 AND
 AND EXTENSION WAS GRANTED TO THE DATE OF
 DEC 31ST, 2005 ONLY. PLEASE BE SURE
 CORRECTED SEAL IS PRESENT WHEN SIGNING
 AND SEALING PLANS.
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  