| 2005-09-10 00:00:00 | *************** UNSAT *********** |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT ALL SPECS/CUT |
| | SHEETS/ MANUFACTURES SHEETS FOR NEW |
| | GENERATOR, ATS, AND SUB-BASE FUEL TANK. |
| | PLEASE SEE REVIEW OF SOME CODE |
| | COMPLIANCE COMMENTS CAN NOT VERIFIED AT |
| | THIS TIME. |
| | |
| | 2)NOTE: PLEASE SEE NEW SERVICE ENTRANCE |
| | RATED ATS/ MAINS SHALL CLEARLY INDICATE |
| | THE MANUAL MEANS OF DISCONNECT LOCATED |
| | ON ON THE OUTSIDE OF EQUIPMENT. |
| | 230.76,230.79. |
| | |
| | 3)NOTE: PLEASE SEE 110.26, 110.26A1 |
| | CONDITION 2 FOR CLEARENCES ABOUT |
| | ELECTRICAL EQUIPMENT. |
| | PLEASE SEE PLANS AS SHOWN FOR LAYOUT |
| | DOES NOT MEET THE MIN OF 3 1/2 FT. |
| | PLEASE ALSO SEE RISER DIAGRAM APPEARS TO |
| | SHOW A NEW GUTTER BEING INSTALLED |
| | DIRECTLY IN-FRONT OF NEW MAINS/ATS. |
| | PLEASE SEE 110.26 WHICH REQUIRES CLEAR |
| | SPACE. IS THIS THE NEW GUTTER BEHINF ATS |
| | MAIN? PLEASE SEE THIS GUTTER IF BEHIND |
| | ATS/ MAINS WILL HAVE LESS THAN 1' FOR |
| | ACCESS?? |
| | |
| | 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS. |
| | PLEASE SEE THAT NEW GENERATOR |
| | ANNUNCIATOR PANEL SHALL BE LOCATED IN |
| | CLOSE PROXIMITY TO ANY EXSITING FACP. |
| | NFPA-101. |
| | |
| | 5)NOTE: PLEASE SEE COLOR CODING OF |
| | FEEDERS FOR 277/480 SHALL BE AS FOLLOWS. |
| | A-BROWN, B-PURPLE AND C- YELLOW. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND AND |
| | STAMPING. |
| | ONE COPY OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | DPALMERWPB.ORG |
| | |