| 2005-09-03 00:00:00 | ******** UNSAT *********** |
| | |
| | ** THE MADISON ** |
| | PLEASE KNOW, PLANS WERE SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AND NOT SUBMITTED FOR |
| | PERMIT. |
| | PLEASE KNOW AS OF OCT 1ST, 2005 THE |
| | STATE OF FLORIDA WILL BE ADOPTED THE NEW |
| | FBC 2004. IF PLANS ETC HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT AND PAID FEES, ANY |
| | DESIGNS WILL THEN BE UNDER THE NEW CODE |
| | REQUIREMENTS. |
| | |
| | |
| | 1)NOTE: PLEASE SEE PERMIT APPLICATION |
| | FOR PLAN REVIEW MENTIONS NEW ELECTRICAL |
| | UNDERGROUND, HOWEVER NO ELECTRICAL PLANS |
| | OR DETAILS WERE SUBMITTED FOR ANY OF |
| | THIS. |
| | IF PLANS WILL BE SUBMITTED FOR |
| | FOUNDATION PERMIT AND ELECTRICAL |
| | UNDERGROUND WORK IS TO BE INCLUDED IN |
| | SCOPE, PROVIDE A DETAIL FOR ALL |
| | UNDERGROUND CONDUITS, SIZES AND |
| | LOCATIONS. |
| | PLEASE ALSO SHOW LOCATIONS OF |
| | MAINS/SERVICES ETC TO BE FED. THESE |
| | LOCATIONS WILL BE REVIEWED FOR CODE |
| | COMPLIANCE.230.72 |
| | PLEASE BE AWARE WITHOUT INFORMATION ON |
| | ELECTRICAL SERVICE,LOADS, SIZES ETC , |
| | ALL UNDERGROUND ELECTRICAL CONDUIT SIZES |
| | FOR FUTURE USE WILL BE AT OWN RISK. |
| | PLEASE SHOW GROUNDING ELECTRODE DETAIL |
| | FOR ANY ATTACHMENTS TO FOOTER/FOUNDATION |
| | STEEL. 250.50,250.66 |
| | |
| | 2)NOTE: PLEASE KNOW, THIS IS A |
| | "THRESHOLD BLDG" AND THREE SETS OF PLANS |
| | WILL BE REQUIRED. |
| | PLEASE ALSO SEE THERE ARE NUMEROUS |
| | SHEETS IN EACH OF THE TWO SETS SUBMITTED |
| | WHICH ARE NOT SIGNED , DATED AND SEALED |
| | AS REQUIRED UNDER FS 471.025. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |