Plan Review Notes
Plan Review Notes For Permit 05081992
Permit Number 05081992
Review Stop E
Sequence Number 4
Notes
Date Text
2006-04-25 00:00:00********** UNSAT 4TH TIME *********
  
 ** PLEASE SEE SOME COMMENTS FROM ALL
 PREVIOUS REVIEWS WHICH STILL NEED TO BE
 ADDRESSED.
 PLEASE ALSO SEE NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS.
  
 1)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCUALTIONS PER SECTION 220.31B OF THE
 NEC>. 2002
  
 2)NOTE: PLEASE SEE PLANS ARE NOW COMING
 BACK WITH RISER CHNAGED AND RISER/PLANS
 DO NOT INDICATE THE OCP AT MAIN SERVICE
 WHICH FEEDS THE NEW SUB-PANEL.
 215.5
  
 3) NOTE: PLEASE SEEMISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN HOUSE
 PANEL TO POOL HOUSE PANEL.
 250.32.
 PLEASE ALSO SEE 250.66 FOR THE MIN
 GROUNDING ELECTRODE CONDUCTOR AT THE
 DETACHED BLDG.
 PLEASE SEE RISER SHOW A #10. THIS IS TOO
 SMALL.
  
 4) NOTE: PLEASE SEE WALL UNIT A/C IS
 SHOWN A 3KW, ON WHAT IS SHOWN ON PLANS
 AS A SINGLE PHASE FEED. PLEASE SEE MAX
 VA FOR 115/120V BRANCH CIRCUIT IS 1440
 FOR 15A OR 1920 FOR 20.
 240.4,310.16 ETC.
  
 5) NOTE: PLEASE SEE THERE IS NOW NO
 PANEL SCHEDULE SUBMITTED TO VERIFY THE
 OCP, AWG FOR BRANCH CIRCUITS OF THIS NEW
 PANEL. WHERE DID THE PANEL SCHEDULE FROM
 PREVIOUS PLANS GO.??
 PLEASE SUBMIT AND PLEASE SEE NEC 2002
 FOR ALL MIN SIZES AS REQUIRED.
  
 6) NOTE: PLEASE SEE ALL BRANCH CIRCUITS
 IN THIS NEW POOL HOUSE SHALL BE ARC
 FAULT.210.12
 PLEASE NOTE, AS ONLY AFCI PROTECTION IS
 NOTED FOR RECEPTS IN BEDRM FOR A/C AND
 GEN PURPOSE RECEPTS.
  
 7) NOTE: PLEASE REVIEW REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED FROM
 SETS AND ONLY TO INSERT NEW SHEETS, THIS
 WAS DONE, HOWEVER PREVIOUS NOTES
 REQUESTED TO SUBMIT ANY OLD/VOIDED
 REMOVED SHEETS AND SUBMIT SEPARATELY.
 PLEASE SEE NO REMOVED SHEETS WERE
 SUBMITTED FOR REFERENCE.
 PLEASE DO SO.
  
 8) NOTE: PLEASE SEE PLANS ARE NOW COMING
 BACK WITH THE TITLE BLOCK FROM THE
 ORIGINAL ENGINEER OF RECORD BEING
 REMOVED FROM ELECTRICLA SHEETS??
 PLEASE SEE FBC ADMINISTRATIVE SECTION
 104.2.1. PLANS WHICH ARE NOT REQUIRED TO
 BE DONE BY ARCHITECT OR ENGINEER, STILL
 MUST CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE DESIGN PROFESSIONAL AND
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 PLEASE SEE PLANS DO NOT CONTAIN EITHER.
  
  
 9) NOTE: PLEASE SEE A NOTICE WAS GIVEN
 ON PERVIOUS REVIEW WHICH STATED
 553.80(2)(B) WHICH RESPECT TO PLANS
 COMING BACK WITH ANY OF THE SAME CODE
 COMLIANCE COMMENTS NOT ADDRESS, A 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE
 PERMIT FEE SHALL BE ACCESSED.
 PLEASE KNOW, THIS IS NOW DONE AND THE
 FEE OF $720 MUST BE PAID BEFORE
 RESUBMITTING PLANS FOR NEXT RESUB.
 IT IS STRONGLY RECOMMENDED A MEETING BE
 HELD TO GO OVER PLANS. THIS MEETING
 SHOULD INCLUDE THE DESIGN PROFESSIONAL
 FOR PROJECT INCLUDING THE ENGINEER,AND
 CONTRACTOR AT A MIN.
 ONE SET OF PLANS ARE BEING RETAINED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]