| 2006-02-06 00:00:00 | ******** UNSAT 3RD REVIEW ********* |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS |
| | REVIEW(S) WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE A MEANS OF DISCONNECT |
| | IS REQUIRED AT THE DETACHED VLDG PER |
| | 225.31 |
| | RISER SHOWS THIS AT MAIN HOUSE? |
| | |
| | 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR |
| | BOTH THE MAIN EXIST PANEL AND NEW SUB |
| | PANEL SHALL BE DONE PER NEC 220,220.31B |
| | ETC. |
| | PLEASE SEE THE LOADS ON NEW SUB PANEL |
| | SHALL CORRELATE WITH THE NEW LOAD ADDED |
| | TO MAIN PANELS. THIS MAY NOT BE DE-RATED |
| | TWICE. |
| | PLEASE SEE THERE IS NO LOCATION IN THE |
| | CODE THAT PERMIT THE FIRST 10 KW AT |
| | 65%?? ETC. |
| | |
| | 3)NOTE: PLEASE SEE SD ADDED TO PLANS, |
| | HOWEVER THIS SD WAS ADDED AND SHOWN |
| | WITHIN 3' OF BATHRM DOOR. PLEASE KNOW, |
| | THIS MUST BE LOCATED MORE THAN 3' FROM |
| | BATH DOOR AS REQUIRED PER NFPA-101 |
| | 11.8.3.5 |
| | |
| | 4)NOTE: PLEASE SEE PREVIOUS PLANS WERE |
| | REDLINED WITH A MISSING RECEPT FOR 2' OF |
| | WALL SPACE. PLEASE SEE THIS WAS ADDED, |
| | HOWEVER THIS HAS BEEN HAND-WRITTEN ON |
| | PLANS WHICH ARE SIGNED, AND SEALED BY AN |
| | ENGINEER. |
| | FS 471.025 |
| | |
| | 5)NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO THE DESIGN PROFESSIONAL AND |
| | REPEAT CODE COMPLIANCE COMMENTS. |
| | PLEAS KNOW, IF PLANS COME BACK WITH ANY |
| | OF THE SAME COMMENT NOT ADDRESSED A 4X |
| | FEE SHALL BE ACCESSED AS REQUIRED PER |
| | STATUE ABOVE AND PLANS SHALL BE RETAINED |
| | FOR POSSIBLE REVIEW BY THE FLORIDA BOARD |
| | OF PROFESSIONAL ENGINEERS. |
| | PLEASE ADDRESS ALL COMMENTS. |
| | |
| | |
| | 6)NOTE: PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH REQUESTED ALL |
| | OLD/VOIDED SHEETS TO BE "REMOVED" FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO SETS FOR REVIEW AND STAMPING. |
| | PLEASE ONLY SUBMIT ONE SET OF OLD SHEETS |
| | FOR REFERENCE. |
| | THIS WAS NOT DONE AND ALL OLD/VOIDED |
| | SHEETS REMAIN IN SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |