Date Text
2005-12-30 00:00:00***********UNSAT ************
  
 1)NOTE: PLEASE SEE 225.31 FOR MEANS OF
 DISCONNECT REQUIRED AT THE DETACHED
 GARAGE. THE RISER SHOWS A DISCONNECT
 ,HOWEVR THIS IS NOT CLEAR WHERE IT IS
 LOCATED.
  
 2)NOTE: PLEASE PROVIDE THE LOAD
 CALCUALTIONS FOR EXISTING DWELLING
 ADDING NEW LOAD OF 34 A'S. PLEASE SEE
 220.31B FOR MIN LOAD CALCS.
 PLEASE PROVIDE THE OCP AT EXISTING HOUSE
 PANEL TO FEED TO SUB PANEL.
  
 3)NOTE: SE REDLINED PLANS FOR MISSING
 RECEPT PER 210.52
  
 4)NOTE: PLEASE SEE NFPA-72 11.5.1.1,
 WHICH WILL REQUIRE A SD INSIDE THIS
 ADAPTABLE SLEEPING AREA. MUST BE 20'
 AWAY FROM COOKING APPLIANCES, OR OF A
 PHOTO-ELECTRIC EYE/RE-SETTING TYPE.
  
 ** PLEASE KNOW, THE RECORDED NOCHAS
 NOW EXPIRED AS PER FS 713.13(2). WORK
 HAS NOTCOMMENCED WITHIN 90 DAYS OF
 RECORDING, THE NOC SHALL BECOME VOID.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  