| Plan Review Notes For Permit 05081992 |
| Permit Number |
05081992 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-12-30 00:00:00 | ***********UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE 225.31 FOR MEANS OF | | | DISCONNECT REQUIRED AT THE DETACHED | | | GARAGE. THE RISER SHOWS A DISCONNECT | | | ,HOWEVR THIS IS NOT CLEAR WHERE IT IS | | | LOCATED. | | | | | | 2)NOTE: PLEASE PROVIDE THE LOAD | | | CALCUALTIONS FOR EXISTING DWELLING | | | ADDING NEW LOAD OF 34 A'S. PLEASE SEE | | | 220.31B FOR MIN LOAD CALCS. | | | PLEASE PROVIDE THE OCP AT EXISTING HOUSE | | | PANEL TO FEED TO SUB PANEL. | | | | | | 3)NOTE: SE REDLINED PLANS FOR MISSING | | | RECEPT PER 210.52 | | | | | | 4)NOTE: PLEASE SEE NFPA-72 11.5.1.1, | | | WHICH WILL REQUIRE A SD INSIDE THIS | | | ADAPTABLE SLEEPING AREA. MUST BE 20' | | | AWAY FROM COOKING APPLIANCES, OR OF A | | | PHOTO-ELECTRIC EYE/RE-SETTING TYPE. | | | | | | ** PLEASE KNOW, THE RECORDED NOCHAS | | | NOW EXPIRED AS PER FS 713.13(2). WORK | | | HAS NOTCOMMENCED WITHIN 90 DAYS OF | | | RECORDING, THE NOC SHALL BECOME VOID. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|